Electrical Application Details for App #: A350525
Premises: 32-08 38 AVENUE QUEENS BIN: 4004584     Block: 381   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 32-08 38TH AV Census Tract:   31 Health Area:  0710
ENTIRE BUILDING Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11101 Community Board:   401
DOB Cross Street(s):    32 STREET,    33 STREET
Status:   C - JOB IS SIGNED OFF 03/20/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/22/2016 9:35 PM
Application Entered:   06/22/2016 Job Start Date:   06/27/2016
Last Change:   03/20/2018 Job End Date:   06/22/2018
Appointment Status:   
Last Inspection By:   ANTOINE FLEMING       On     02/20/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011853 Licensee Name: APPOLINAIRE LAUTURE
Firm: 004819 Firm Name: APPO ELECTRICAL CONTRS IN
Firm Phone: 718-726-0814  Firm Address: 32-08 38TH AVENUE LONG ISLAND CITY NY 11101 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011853 LAUTURE, APPOLINAIRE 003458 APPO ELECTRICAL, LLC

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $186.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VASHIE RAMLOCHAM
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  SETS 0F # 2 WIRE
B. 101 Up to 200 AMPS  1  SET OF # 3/0 WIRE
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  SETS OF # 2 WIRE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1   SET OF # 3/0 WIRE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    10                 
001    12  16                 
002                 
003    10  12               
Buildings Total 36  40  14                  
Total Units : 93 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 1 #10-Wire 0
Existing Meters 3 + New Meters 0 - Removed Meters 0 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/22/2016 Notice: 1 - FIRST NOTICE 02/06/2018
Power Issued: 06/22/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A350525
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/02/2018 02/06/2018 GBZ V (55) (5)
INSPECTION COMMENTS: FAIL
 
(2) 02/20/2018 02/20/2018 AGF C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED... PASS|||

OBJECTION FOR APPLICATION #: A350525
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(GROUND FLOOR) UNDERSIZE SER CONDUCTOR
RSLV 02/02/2018 02/02/2018 02/20/2018
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(GROUND FLOOR) PANEL IN GARAGE,
RSLV 02/02/2018 02/02/2018 02/20/2018
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(GROUND FLOOR) GARAGE
RSLV 02/02/2018 02/02/2018 02/20/2018
 
004 (999) OTHER
(GROUND FLOOR) NO SIMULTANEOUS DISCONNECT ON MULT WIRE 210.4
RSLV 02/02/2018 02/02/2018 02/20/2018
 
005 (999) OTHER
(GROUND FLOOR) MULT WIRE NOT GROUPED 210.4
RSLV 02/02/2018 02/02/2018 02/20/2018