Electrical Application Details for App #: A350507
Premises: 31-77 37 STREET QUEENS BIN: 4617478     Block: 657   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 31-77 37TH ST Census Tract:   61 Health Area:  0400
ENTIRE Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11103 Community Board:   401
Related Job Number:    421042455
DOB Cross Street(s):    31 AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 07/25/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/22/2016 2:46 PM
Application Entered:   06/22/2016 Job Start Date:   06/22/2016
Last Change:   07/25/2017 Job End Date:   06/27/2017
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     07/20/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011143 Licensee Name: GIUSEPPE A MALATESTA
Firm: 002526 Firm Name: LTC ELECTRIC INC.
Firm Phone: 718-205-3334  Firm Address: 102-30 CORONA AVENUE CORONA NY 11368 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $2,679.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN RESTANI
Owner Business Name: 37 BROADWAY LLC
Authorized Representative:  JOHN RESTANI
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1 - 30 AMP
B. 101 Up to 200 AMPS  1  1 - 200 AMP
C. 201 Up to 600 AMPS  2  2 - 400 AMP
D. 601 Up to 1200 AMPS  1  1 - 800 AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  30  30 - #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  4 - 3/0
D. Over 250 MCM  7  5 - 500 MCM 2 - 350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  27  27 - 20 CKT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  7  5 - 200 AMP 2 - 100 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    30  12    10  30  12         
001  1 FL  87  80    33  87             
002  2 FL  40  20    36  40             
003  3 FL  40  20    36  40             
004  4 FL  40  20    36  40             
005  5 FL  40  20    36  40             
ROF    15    77         
Buildings Total 285  187    190  285     89           
Total Units : 1036 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 27 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 29 - Removed Meters 0 = Total Meters 29

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/22/2016 Notice: 1 - FIRST NOTICE 07/11/2017
Power Issued: 06/22/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ENTIRE - NEW 5-STORY 27-FAMILY RESIDENTIAL DWELLING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A350507
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/11/2017 07/11/2017 EVG V (180) (3)
INSPECTION COMMENTS: JOB FAILED.
 
(2) 07/20/2017 07/20/2017 DEX C R (40) (0)
INSPECTION COMMENTS: DISPUTES RESOLVED

OBJECTION FOR APPLICATION #: A350507
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001)APT - 1E, 1A, 1C, 1B AND 2A NEED EXTENSION COLLARS FOR THE MICROWAVERECEPTACLES.
RSLV 07/11/2017 07/11/2017 07/20/2017
 
002 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
(ALL FLOORS)UNDER CABINETS LIGHTS AND COUNTER GFCI RECEPTACLE ARE ON THE SAMECIRCUIT.
RSLV 07/11/2017 07/11/2017 07/20/2017
 
003 (999) OTHER
(BASEMENT)NO BONDING BUSHING FOR SERVICE SWITCH #2, FOR THE METER BANK.
RSLV 07/11/2017 07/11/2017 07/20/2017