BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A349231
Premises: 30-89 38 STREET QUEENS BIN: 4616399     Block: 660   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 30-89 38 ST Census Tract:   155 Health Area:  0520
38 STREET Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11103 Community Board:   401
Related Job Number:    420102953
DOB Cross Street(s):    30 AVENUE,    31 AVENUE
Status:   C - JOB IS SIGNED OFF 07/20/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/18/2016 4:22 PM
Application Entered:   05/18/2016 Job Start Date:   05/18/2016
Last Change:   07/20/2016 Job End Date:   05/18/2017
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     07/07/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012170 Licensee Name: IVAN BUTKOVIC
Firm: 003881 Firm Name: EINSTEIN ELEC'L CORP
Firm Phone: 718-274-7600  Firm Address: 42-16 28TH AVENUE, 2ND FL ASTORIA NY 11103 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,436.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EUGEN KULJANIC
Owner Business Name: ST IVAN LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1-400A
D. 601 Up to 1200 AMPS  1  1-600 A 3 PHASE
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  10  10 SETS 3 CONDUCTOR #4 TH
B. Over #2 to 1/0  1  1 SET #2 THHN
C. Over 1/0 to 250 MCM  2  2 SET 3/0 THHN
D. Over 250 MCM  3  1-500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  SINGLE PHASE 70A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  2-200A,1-100A
D. 3 Phase Over 225 AMPS  1  1-400A 3 PHASE
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    52  22    20             
001    20  52    13  143             
002    12  46  20  34             
003    19  43  24  30             
004    17  51  24  30             
005    12  46  18  34             
Buildings Total 132  260  10  119  273                
Total Units : 794 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 3 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/18/2016 Notice: 1 - FIRST NOTICE 06/13/2016
Power Issued: 05/18/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB WAS DONE BY OTHERS , OWNER HIRED US TO FILE AND INSPECTWORK

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A349231
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/10/2016 06/13/2016 GBZ V (85) (4)
INSPECTION COMMENTS: NONE
 
(2) 07/07/2016 07/07/2016 WYF C R (52) (0)
INSPECTION COMMENTS: ALL OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: A349231
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) HANDLE TIES NOT PROVIDED THRU OUT BLDG ART 210.4B
RSLV 06/10/2016 06/10/2016 07/07/2016
 
002 (279) WATER METER JUMPER IS MISSING/IMPROPER
(BASEMENT) WATER METER NO JUMPER ART 250.53C
RSLV 06/10/2016 06/10/2016 07/07/2016
 
003 (999) OTHER
(BASEMENT) LINE SIDE BONDING NOT PROVIDED 400AMP ART250.92
RSLV 06/10/2016 06/10/2016 07/07/2016
 
004 (999) OTHER
(ROOF) OUTLET NOT TR WR ART 406.11/406.8
RSLV 06/10/2016 06/10/2016 07/07/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order