NYC Department of Buildings
Electrical Application Details for App #: A348950
Premises: 41-07 CRESCENT STREET QUEENS BIN: 4005008     Block: 415   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41-07 CRESCENT ST Census Tract:   33
BSMT,1 THRU 9 FLRS & ROOF Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11101 Community Board:   401
Related Job Number:    420871809
DOB Cross Street(s):    41 AVENUE,    QUEENS PLAZA NORTH
Status:   C - JOB IS SIGNED OFF 07/27/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/10/2016 Job Start Date:   05/13/2016
Last Change:   07/27/2016 Job End Date:   12/20/2016
Appointment Status:   
Last Inspection By:   BASDEO, C       On     07/27/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011398 Licensee Name: JOSEPH FERGUSON
Firm: 003192 Firm Name: AVALON ELECTRIC CORP.
Firm Phone: 718-543-2327  Firm Address: 5760 BROADWAY 2ND FLOOR BRONX NY 10463 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  420871809
Building Used As:   Z - Commercial/Residential (1  Stores, 47 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53215     Submittal #: 15A0353  
Owner / Occup: SHELDON STEIN
Owner Business Name: 41-07 CRESCENT JV LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  600A 3PHASE
E. Over 1200 AMPS  3  2-800A, 1-1200A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  47  (45)#4 THHN & (2)#6 THHN
B. Over #2 to 1/0  3  #3 THHN
C. Over 1/0 to 250 MCM  7  #3/0 THHN
D. Over 250 MCM  141  4-#400,6-#500,2#600,2-350
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  47  125A MLO 30 CIRCUIT
C. 3 Phase Up to 225 AMPS  7  200A MLO 42 CIRCUIT
D. 3 Phase Over 225 AMPS  1  800A MDP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  100A
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  12  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    38  13    38  10  15         
GND    83  10    12  83  13         
002    97  162  16  72  97             
003    97  162  16  72  97             
004    97  162  16  72  97             
005    97  162  16  72  97             
006    97  162  16  72  97             
007    98  158  17  64  98             
008    97  158  17  64  98             
009    81  67  25  81         
ROF      21     
Buildings Total 886  1220  118  534  887     53         
Total Units : 3701 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 47 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 48 - Removed Meters 0 = Total Meters 48

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/10/2016 Notice: 1 - FIRST NOTICE 06/22/2016
Power Issued: 05/10/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS PERMIT SUPERSEDE PERMITS A342939 & A334603

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A348950
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/22/2016 06/22/2016 COB V (180) (4)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 07/27/2016 07/27/2016 COB C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: A348950
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT)SERVICE ROOM, FIRE ALARM FUSE CUT OUT, LINE SIDE NOT BONDED
RSLV 06/22/2016 06/22/2016 07/27/2016
 
002 (999) OTHER
(BASEMENT)SERVICE ROOM, GROUNDING RACEWAY NOT CONTINUOUS TO COPPER DETAIL -250.64(E)
RSLV 06/22/2016 06/22/2016 07/27/2016
 
003 (999) OTHER
(BASEMENT) SERVICE ROOM, DOORS, PANIC BAR NOT PROVIDED - 110.26.C.2
RSLV 06/22/2016 06/22/2016 07/27/2016
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(ROOF) GENERATOR, GROUNDING CONDUCTOR TO WATER MAIN REQUIRED
RSLV 06/22/2016 06/22/2016 07/27/2016