BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A344774
Premises: 120-55 QUEENS BOULEVARD QUEENS BIN: 4052812     Block: 2274   Lot: 2
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 120-55 QUEENS BLVD Census Tract:   216
GROUND FLOOR Admin Area:   A - QUEENS Inspection Area:   H
QUEENS, NY 11415 Community Board:   409
Special Place Name:   QUEENS BOROUGH HALL FORUM
DOB Cross Street(s):   CONNECTOR ROAD TO UNION TPKE EB,    82 AVENUE
Status:   C - JOB IS SIGNED OFF 07/20/2016
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   01/06/2016 Job Start Date:   01/08/2016
Last Change:   07/20/2016 Job End Date:   01/10/2016
Appointment Status:   
Last Inspection By:   WONG, K.       On     07/20/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011473 Licensee Name: JOHN MANNINO
Firm: 002318 Firm Name: UP TOWN ELECTRIC INC
Firm Phone: 718-359-8210  Firm Address: 516 INDUSTRIAL LOOP,SUITE 201 STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $715.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53315     Submittal #: 15A0512  
Owner / Occup: JOSEPH WAGNER
Owner Business Name: DCAS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/17/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A344774
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/17/2016 02/17/2016 ECH V (29) (3)
INSPECTION COMMENTS: NONE
 
(2) 07/19/2016 07/20/2016 KIW J Y (40) (0)
INSPECTION COMMENTS: NO FIRE STOPPING
 
(3) 07/20/2016 07/20/2016 KIW C R (30) (0)
INSPECTION COMMENTS: OK, FIRE STOPPING INSTALLED.

OBJECTION FOR APPLICATION #: A344774
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(GROUND FLOOR) SWITCH SIZE IS 2000A BUT PRINT CALLS FOR 1600
RSLV 02/17/2016 02/17/2016 07/19/2016
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(GROUND FLOOR) PRINT CALLS FOR 15' TAP, ACTUAL TAP IS 25'
RSLV 02/17/2016 02/17/2016 07/19/2016
 
003 (999) OTHER
(GROUND FLOOR)FIRE STOPPING HAS NOT BEEN PERFORMED IN ELECTRICAL ROOM PER ART.300.21
RSLV 02/17/2016 02/17/2016 07/20/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order