| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(291) |
BATHROOM RECEPTACLE NOT PROPERLY LOCATED (FLOOR: 001) FRONT BEDROOM BATH GFCI NO TPROPERLY LOCATED |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 002 |
(999) |
OTHER (FLOOR: 001) GFCI NOT PROVIDED FOR KITCHEN COUNTER ART 210.52B |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 003 |
(999) |
OTHER (FLOOR: 001) NO GFCI PROVIDED FOR PENINSULA |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 004 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 002) MASTER BATH GFCI RIGHT NO POWER |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 005 |
(290) |
BATHROOM BRANCH CIRCUIT NOT PROVIDED (FLOOR: 002) BATH LIGHTS AND GFCIS ON SAME CIRCUIT |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 006 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 002) MASTER BEDROOM NO AFCI FOR LIGHTS |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 007 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ATTIC) LIGHTS GROUND NOT TERMINATED |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 008 |
(999) |
OTHER (ATTIC) NO QUICK CONNECTS FOR LIGHTS ART 410.130G |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 009 |
(999) |
OTHER (ATTIC) WIRES NOT PROTECTED FEEDING FIXTURES ART 110.3 |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 010 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE (BASEMENT) SUB PANEL AFCI DEFECTIVE |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 011 |
(279) |
WATER METER JUMPER IS MISSING/IMPROPER (BASEMENT) WATER METER NO JUMPER |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 012 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (BASEMENT) OPEN KO IN SUB PANEL |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 013 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (BASEMENT) LAUNDRY ROOM NO GFCI PROVIDED |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 014 |
(999) |
OTHER (BASEMENT)INSUFFICIENT RECEPTACLES IN BASEMENT BATHROOM WALL ART 210.52A1 |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 015 |
(999) |
OTHER (BASEMENT) SPLICE BOX BURIED IN CEILING FOR GARAGE FEED |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |
| |
| 016 |
(999) |
OTHER (OPEN SPACE) NO SERVICE RECEPTACLE PROVIDED FOR ACS ART 210.63 |
RSLV |
08/23/2017 |
08/23/2017 |
10/02/2017 |