BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A342662
Premises: 41-29 24 STREET QUEENS BIN: 4594898     Block: 414   Lot: 117
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 41-29 24 ST Census Tract:   33 Health Area:  0710
ALL BUILDING Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11101 Community Board:   401
Related Job Number:    410147461
DOB Cross Street(s):    41 AVENUE,    QUEENS PLAZA NORTH
Status:   C - JOB IS SIGNED OFF 10/06/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/27/2015 3:19 PM
Application Entered:   10/27/2015 Job Start Date:   10/27/2015
Last Change:   10/06/2017 Job End Date:   06/25/2017
Appointment Status:   
Last Inspection By:   GLENN BALZARANO       On     08/30/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010786 Licensee Name: JOE ZAGO
Firm: 004257 Firm Name: ROMA ELECTRIC CORP
Firm Phone: 718-777-7662  Firm Address: 30-75 14TH STREET ASTORIA NY 11102 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
T - TEMPORARY LIGHT & POWER
Total Fee:  $4,726.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  410147461
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH D CIAMPA
Owner Business Name: CIAMPA 24 LLC
Authorized Representative:  CIAMPA JOSEPH
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  1-400A, 2-600A
D. 601 Up to 1200 AMPS  1  1200A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  82  45-3#6, 30-3#4, 6-3#3, #2
B. Over #2 to 1/0  1  4#1/0
C. Over 1/0 to 250 MCM  2  4#3/0
D. Over 250 MCM  7  3-4#500MCM, 4-4#350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  79  79 - 100A
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  2-100A, 3-200A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    44  26    44  69         
001    54  130    40  54         
002    50  148    40  50             
003    50  148    40  50             
004    50  148    40  50             
005    50  148    40  50             
006    50  148    40  50             
007    50  148    40  50             
008    50  148    40  50             
009    50  148    40  50             
010    50  148    40  50             
011    38  18    38  12  46         
ROF      11  128         
Buildings Total 590  1510    415  590     249           
Total Units : 3354 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 79 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/27/2015 Notice: 1 - FIRST NOTICE 08/07/2017
Power Issued: 10/27/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WILL PERFORM ALL ELECTRICAL TRADE WORK FOR THE CONSTRUCTIONOF THIS NEW BUILDING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A342662
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/27/2017 07/28/2017 WYF J (29) (0) Y
INSPECTION COMMENTS: INSPECTED SERVICE ONLY NOT ENOUGH TIME ON JOB TO COMPLETE INSPECTION
 
(2) 08/07/2017 08/07/2017 ECH V (192) (3)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(3) 08/30/2017 08/30/2017 GBZ C R (46) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: A342662
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (114) GFCI HAS NOT BEEN PROVIDED FOR BATHROOM RECEPTACLES
(ALL FLOORS)ALL BATHROOMS ABOVE MIRROR RECEPTACLE MUST BE GFCI PROTECTED 210.8
RSLV 08/07/2017 08/07/2017 08/30/2017
 
002 (999) OTHER
(CELLAR)LIGHT FIXTURES IN LAUNDRY ROOM NOT SUPPORTED WITH LISTED CLIPS410.10
RSLV 08/07/2017 08/07/2017 08/30/2017
 
003 (999) OTHER
(ROOF) WATER FOUNTAIN MUST HAVE GFCI PROTECTION 422.52
RSLV 08/07/2017 08/07/2017 08/30/2017