Electrical Application Details for App #: A342190
Premises: 55-27 MYRTLE AVENUE QUEENS BIN: 4082442     Block: 3451   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 55-27 MYRTLE AV Census Tract:   551 Health Area:  2300
CELLAR TO 5TH Admin Area:   A - QUEENS Inspection Area:   G
QUEENS, NY 11385 Community Board:   405
DOB Cross Street(s):   MADISON STREET,    PUTNAM AVENUE
Status:   C - JOB IS SIGNED OFF 07/11/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/11/2015 12:40 PM
Application Entered:   10/11/2015 Job Start Date:   10/14/2015
Last Change:   07/11/2017 Job End Date:   10/14/2016
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     07/05/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011755 Licensee Name: MICHAEL DIDONATO
Firm: 004343 Firm Name: DIDONATO & SONS ELCL CONT
Firm Phone: 718-269-0217  Firm Address: 85 INDUSTRIAL LOOP CORP STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $3,151.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH HOFFMAN
Owner Business Name: BUSHBURG PROPERTIES
Authorized Representative:  JOSEPH HOFFMAN
Relationship To Owner:   BUILDER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  3  1 200AMP/1 600 AMP/1 2500
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  8SETS 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  50  100 AMP 24 CIRCUIT
C. 3 Phase Up to 225 AMPS  3  3 200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  CEL  20  24                 
001  36  100    24    50     
002  36  100    24               
003  36  100    24               
004  36  100    24               
005  36      24               
Buildings Total 200  424    128              
Total Units : 755 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 50 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 51 - Removed Meters 0 = Total Meters 51

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/11/2015 Notice: C - CALL TO OFFICE 05/23/2017
Power Issued: 10/11/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  50 APTS AND PLP

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A342190
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/10/2017 01/10/2017 ECH V (179) (12)
INSPECTION COMMENTS: SERVICE NOT INSPECTED, CONTRACTOR MUST RE-FILE FOR SERVICE ADVISORY BOARD APPROVAL REQUIRED
 
(2) 04/24/2017 04/24/2017 ECH V R (209) (3)
INSPECTION COMMENTS: SEE OBJECTIONS
 
(3) 05/23/2017 05/23/2017 ECH J X (50) (0) Y
INSPECTION COMMENTS: NO UPDATED APPROVED DRAWINGS
 
(4) 07/05/2017 07/05/2017 ECH C R (110) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: A342190
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 005) 501 COVER MISSING FROM REFRIGERATOR RECEPTACLE 406.5
RSLV 01/10/2017 01/10/2017 04/24/2017
 
002 (999) OTHER
(FLOOR: 005)SINGLE RECEPTACLE UNDER SINK NOT TAMPER RESISTANT 406.11
RSLV 01/10/2017 01/10/2017 04/24/2017
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) ALL APARTMENTS VERIZON AND CLOSET RECEPTACLE
RSLV 01/10/2017 01/10/2017 04/24/2017
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) ALL APARTMENTS WASHING MACHINE RECEPTACLE IN CLOSET
RSLV 01/10/2017 01/10/2017 04/24/2017
 
005 (999) OTHER
(ALL FLOORS)ALL APARTMENT A/C BLOWER UNITS OVER FUSED, PER MANUFACTURER SPEC.SHOULD BE 15 AMP
RSLV 01/10/2017 01/10/2017 04/24/2017
 
006 (999) OTHER
(ALL FLOORS)COUNTER-TOP RECEPTACLE BOXES SET MORE THEN 1/4" BACK 314.20
RSLV 01/10/2017 01/10/2017 04/24/2017
 
007 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR) CONTRACTOR MUST SEEK ADVISORY BOARD APPROVAL
RSLV 01/10/2017 01/10/2017 04/24/2017
 
008 (999) OTHER
(CELLAR) RECEPTACLE BOXES IN LOUNGE SET MORE THEN 1/4" BACK 314.20
RSLV 01/10/2017 01/10/2017 04/24/2017
 
009 (999) OTHER
(CELLAR)SERVICE ROOM REQUIRES PANIC BARS ON ALL DOORS PER 110.26(C)(3)
RSLV 01/10/2017 01/10/2017 04/24/2017
 
010 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ROOF) AT LEAST 2 RECEPTACLES ON ROOF DO NOT WORK
RSLV 01/10/2017 01/10/2017 04/24/2017
 
011 (999) OTHER
(ROOF)OUTDOOR ROOF RECEPTACLES ON WALLS MUST BE WEATHER RESISTANT TYPE406.8
RSLV 01/10/2017 01/10/2017 04/24/2017
 
012 (999) OTHER
(ROOF) UPPER ROOF RECEPTACLE MISSING COVER 406.8
RSLV 01/10/2017 01/10/2017 04/24/2017
 
013 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) FIRE PUMP ON PRINT (75HP) DOES NOT MATCH ACTUAL PUMP (25HP)
RSLV 04/24/2017 04/24/2017 07/05/2017
 
014 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) FIRE PUMP FUSE SIZE
RSLV 04/24/2017 04/24/2017 07/05/2017
 
015 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) FIRE PUMP CONDUCTOR SIZE
RSLV 04/24/2017 04/24/2017 07/05/2017