BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A341986
Premises: 26-26 JACKSON AVENUE QUEENS BIN: 4003502     Block: 267   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 26-26 JACKSON AV Census Tract:   19 Health Area:  0720
GROUND FLOOR Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Special Place Name:   ASTORIA BANK
DOB Cross Street(s):   PURVES STREET,    43 AVENUE
Status:   C - JOB IS SIGNED OFF 02/25/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/05/2015 10:39 AM
Application Entered:   10/05/2015 Job Start Date:   10/05/2015
Last Change:   02/25/2016 Job End Date:   10/15/2015
Appointment Status:   
Last Inspection By:   BASDEO, C       On     02/25/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011364 Licensee Name: RAYMOND B MCQUILLAN
Firm: 002779 Firm Name: CORP. ELEC'L TECHNOLOGIES
Firm Phone: 718-857-1521  Firm Address: 94-02 LINDEN BLVD 1ST FLOOR (INC.) OZONE PARK NY 11417 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $295.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL BANKING BRANC
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL PERROTTA
Owner Business Name: EAGLE INTERIORS INC
Authorized Representative:  MICHAEL PERROTTA
Relationship To Owner:   CONSTRUCTION MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400A COMBO
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  1-4#500
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  400 MDP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/05/2015 Notice: 1 - FIRST NOTICE 12/09/2015
Power Issued: 10/05/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ASTORIA BANK - SERVICE WORK - REPLACMENT OF MDP AND SET NEW METER IN EXISTING METER SOCKET.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A341986
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/08/2015 12/09/2015 COB V (38) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 02/25/2016 02/25/2016 COB C R (49) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: A341986
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) LINE SIDE OF 400ASERVICE SWITCH
RSLV 12/08/2015 12/08/2015 02/25/2016
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT) HANGING CONDUCTORS TO BE TERMINATED IN BOS
RSLV 12/08/2015 12/08/2015 02/25/2016
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) WATER MAIN GROUND NOT INSTALLED AND NOT TO NEUTRAL
RSLV 12/08/2015 12/08/2015 02/25/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order