BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A340906
Premises: 89-07 169 STREET QUEENS BIN: 4209733     Block: 9803   Lot: 15
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 89-07 169 ST Census Tract:   460 Health Area:  2810
ROOF Admin Area:   A - QUEENS Inspection Area:   J
QUEENS, NY 11432 Community Board:   412
Special Place Name:   JAMAICA
DOB Cross Street(s):    89 AVENUE,    90 AVENUE
Status:   C - JOB IS SIGNED OFF 04/02/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/31/2015 7:42 AM
Application Entered:   08/31/2015 Job Start Date:   09/02/2015
Last Change:   04/02/2016 Job End Date:   09/05/2015
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     03/29/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011316 Licensee Name: RALPH J RUSSO
Firm: 002733 Firm Name: RJ RUSSO ELECTRIC CO.
Firm Phone: 718-423-4742  Firm Address: 45-57 BELL BLVD BAYSIDE NY 11361 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
E - SUSTAINABLE ENERGY - SOLAR
Total Fee:  $241.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   J - Theatre
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DENNIS MULLARKEY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  #2 AND#6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3   PANELS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                      60 
ROF              139  36         
Buildings Total              36          60 
Total Units : 96 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/10/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SOLAR INSTALL,139 255 WATT PV MODULES,TOTAL 35,445 WATTS DC,2 ARRAYS 3 STRINGS,2 INVERTERS ,1 PANEL 1 TRANSFORMER, 1 MAIN DISCONNECT.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A340906
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2016 02/10/2016 ECH V (90) (3)
INSPECTION COMMENTS: APPROVED DRAWING HAS BEEN ALTERED
 
(2) 03/29/2016 03/30/2016 DEX C R (30) (0)
INSPECTION COMMENTS: JOB IS OK

OBJECTION FOR APPLICATION #: A340906
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(CELLAR)APPROVED ONE LINE DIAGRAM NOT PROVIDED AT TIME OF INSPECTION AMEND.690.1
RSLV 02/10/2016 02/10/2016 03/29/2016
 
002 (999) OTHER
(CELLAR) WIRE SIZE NOT PER ONE LINE DIAGRAM AMENDMENT 690.1
RSLV 02/10/2016 02/10/2016 03/29/2016
 
003 (999) OTHER
(CELLAR)GROUNDING ELECTRODE SYSTEM NOT PROVIDED PER ART.690.47 AND 1 LINEDIAGRAM
RSLV 02/10/2016 02/10/2016 03/29/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order