BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A339874
Premises: 44-11 PURVES STREET QUEENS BIN: 4595482     Block: 267   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 44-11 PURVES ST Census Tract:   19 Health Area:  0720
BASEMENT AND ROOF Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
DOB Cross Street(s):   JACKSON AVENUE,    DEAD END
Status:   C - JOB IS SIGNED OFF 02/19/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/27/2015 1:42 PM
Application Entered:   07/27/2015 Job Start Date:   07/27/2015
Last Change:   02/19/2016 Job End Date:   11/27/2015
Appointment Status:   
Last Inspection By:   POMERICO, RAYMOND E       On     01/26/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012537 Licensee Name: RU W HUANG
Firm: 004357 Firm Name: ATMOS ELECTRIC SVCE CORP
Firm Phone: 718-888-1501  Firm Address: 15-25 132 STREET 2ND FLOOR COLLEGEPOINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
E - SUSTAINABLE ENERGY - SOLAR
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: EXCEL BRADSHAW MGMT GROUP
Authorized Representative:  ANTHONY PASSALACQUA
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #4 SINGLE PHASE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/25/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL SOLAR PV PANEL AND METER. INSTALL A FEEDER FROM BASEMENT TO ROOF.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A339874
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/19/2015 11/25/2015 COB A (40) (5) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 01/06/2016 01/06/2016 TS1 J Y (38) (0)
INSPECTION COMMENTS: NEED DIAGRAM
 
(3) 01/26/2016 01/26/2016 RYP C R (51) (0)
INSPECTION COMMENTS: ONE-LINE DRAWING SUPPLIED (DID NOT KEEP), CORRECTED; CERTIFIED

OBJECTION FOR APPLICATION #: A339874
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)ROOF AND BASEMENT DOB APPROVED ONE LINE DIAGRAM NOT PROVIDED 690.1 NYC AMEND
RSLV 11/19/2015 11/19/2015 01/26/2016
 
002 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) BASEMENT PANEL USED AS RACEWAY TO FEED OTHER PANEL
RSLV 11/19/2015 11/19/2015 01/06/2016
 
003 (999) OTHER
(ALL FLOORS) BASEMENT ROOF LABELS NOT PROVIDED 690.5(C)
RSLV 11/19/2015 11/19/2015 01/06/2016
 
004 (999) OTHER
(ALL FLOORS)ROOF CABLE FROM ROOF TO BASEMENT APPROVED CABLE SUPPORT AND JUNCTION BOXES AT THE REQUIRED INTERVALS NOT PROVIDED 300.19(C)
RSLV 11/19/2015 11/19/2015 01/06/2016
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) ROOF DC COMBINER PANEL BREAKER SPACE OPEN
RSLV 11/19/2015 11/19/2015 01/06/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.