BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A339384
Premises: 31-15 14 STREET QUEENS BIN: 4005885     Block: 533   Lot: 21
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 3115 14 ST Census Tract:   77 Health Area:  0300
1ST FLOOR Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
Special Place Name:   SKYLINE ENGINEERING
DOB Cross Street(s):    31 AVENUE,    31 ROAD
Status:   C - JOB IS SIGNED OFF 04/16/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/13/2015 12:34 PM
Application Entered:   07/13/2015 Job Start Date:   07/13/2015
Last Change:   04/16/2016 Job End Date:   07/13/2015
Appointment Status:   
Last Inspection By:   SAMARAS TASOS       On     12/14/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011990 Licensee Name: DECLAN W DELAHUNTY
Firm: 003662 Firm Name: SHUIR ELEC'L CONTR'S CORP
Firm Phone: 718-414-4840  Firm Address: 4360 BULLARD AVENUE BRONX NY 10466 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $62.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MATT WAVRO
Owner Business Name: SKYLINE ENGINEERING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  40  30    10      16     
Buildings Total 40  30    10          16      
Total Units : 98 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/27/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRE OFFICE SPACE FROM EXISTING ELECTRICAL PANEL.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A339384
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/23/2015 11/27/2015 EVG A (40) (3) Y
INSPECTION COMMENTS: VIOLATIONS. UNITS ON THE ROOF AREA TO BE FUSED AT 15A MAX, 35A MAX AND 35A MAX
 
(2) 12/14/2015 12/14/2015 TS1 C R (30) (0)
INSPECTION COMMENTS: JOB PASS

OBJECTION FOR APPLICATION #: A339384
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) PANEL MISSING HANDLE TIES FOR BRANCH CKTS 210.4G
RSLV 11/23/2015 11/23/2015 12/14/2015
 
002 (999) OTHER
(ALL FLOORS) SVC NO INTERSYSTEM BAR 250.94
RSLV 11/23/2015 11/23/2015 12/14/2015
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) ROOF A.C. UNITS OVERFUSED THROUGHOUT
RSLV 11/23/2015 11/23/2015 12/14/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back