BIS Menu  |  Property Profile  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A338855
Premises: 54-05 SKILLMAN AVENUE QUEENS BIN: 4594818     Block: 1239   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 54-25 SKILLMAN AV Census Tract:   251 Health Area:  0920
GROUND FLOOR Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11377 Community Board:   402
Special Place Name:   PS11Q
DOB Cross Street(s):    55 STREET,    56 STREET
Status:   C - JOB IS SIGNED OFF 08/07/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/25/2015 10:30 AM
Application Entered:   06/25/2015 Job Start Date:   06/26/2015
Last Change:   08/07/2019 Job End Date:   07/31/2015
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     07/29/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  

License #: 012658 Licensee Name: JAMES M CARDILLO
Firm: 000648 Firm Name: HELLMAN ELECTRIC LLC
Firm Phone: 718-931-9900  Firm Address: 855 BRUSH AVENUE BRONX NY 10465 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
011333 LAZZARO, STEVEN 000648 HELLMAN ELECTRIC LLC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
Total Fee:  $565.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANTONIO GENTILE
Owner Business Name: NYCSCA
Authorized Representative:  JOHN KRECKEL
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  1200A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  4-600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  1200A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/25/2015 Notice:  
Power Issued: 06/25/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A338855
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/29/2019 07/29/2019 ECH C (15) (0) Y
INSPECTION COMMENTS: PASS, TEMP SERVICE IS NOT PRESENT AT TIME OF INSPECTION




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Profile  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back