Electrical Application Details for App #: A337389
Premises: 86-49 BROADWAY QUEENS BIN: 4045397     Block: 1842   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 8655 BROADWAY Census Tract:   473 Health Area:  1420
208 Admin Area:   A - QUEENS Inspection Area:   D
QUEENS, NY 11373 Community Board:   404
DOB Cross Street(s):   JUSTICE AVENUE,    GRAND AVENUE
Status:   C - JOB IS SIGNED OFF 01/30/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/11/2015 1:03 PM
Application Entered:   05/11/2015 Job Start Date:   05/11/2015
Last Change:   01/30/2017 Job End Date:   06/11/2015
Appointment Status:   
Last Inspection By:   GLENN BALZARANO       On     01/30/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 012521 Licensee Name: JUAN C ROMERO-LIMA
Firm: 004340 Firm Name: ROMERO ELECTRIC LLC
Firm Phone: 718-396-0604  Firm Address: 700 WEST 192ND STREET 2ND NEW YORK NY 10040 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $135.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (8  Stores, 208 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SPERINA SAN
Owner Business Name: STRUCTURAL LAND MANAGEMEN
Authorized Representative:  SAN SPERINA
Relationship To Owner:   GC


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4# 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200AMP--3 PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 1 + New Meters 2 - Removed Meters 1 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/11/2015 Notice: C - CALL TO OFFICE 12/22/2016
Power Issued: 05/11/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALL A 400 AMP METER , TWO 200 AMP DISCONNECT SWITCH ANDINSTALL A 200 AMP FEEDER AND SUB PANEL

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A337389
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/30/2015 07/06/2015 COB V G (45) (3) Y
INSPECTION COMMENTS: VIOLATIONS. TROUGH OPEN 200A DISCONNECT NOT CONNECTED IN SERVICE ROOM
 
(2) 06/29/2016 06/30/2016 LUF H X (30) (0) Y
INSPECTION COMMENTS: OBJECTIONS NOT REMOVED ,INSPECTOR WAS NOT GIVEN ADVISORY BOARD DRAWINGS
 
(3) 07/18/2016 07/18/2016 GBZ V R (24) (2)
INSPECTION COMMENTS: NONE
 
(4) 12/21/2016 12/22/2016 NRS J X (35) (0) Y
INSPECTION COMMENTS: -NO STAMPED ADVISORY BOARD DRAWING PROVIDED.
 
(5) 01/30/2017 01/30/2017 GBZ C R (24) (0)
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: A337389
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(ALL FLOORS)BASEMENT ELECTRICAL SERVICE ROOM 400A SECOND FUSE TAP, REQUIRED ADVISORY BOARD APPROVAL
RSLV 06/30/2015 06/30/2015 07/18/2016
 
002 (999) OTHER
(ALL FLOORS)BASEMENT SERVICE ROOM TRAN-S METER PANEL NEUTRAL BAR BONDED AFTER SERVICE 250.34A(5)
RSLV 06/30/2015 06/30/2015 07/18/2016
 
003 (999) OTHER
(ALL FLOORS)BASEMENT SERVICE ROOM DOORS FOR EQUIPMENT 1200A AND LARGER SHALL BE EQUIPPED WITH PANIC BARS 110.26.C.2
RSLV 06/30/2015 06/30/2015 07/18/2016
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
(CELLAR) SWITCH GEAR OPENINGS COVERED WITH CARD BOARD
RSLV 07/18/2016 07/18/2016 01/30/2017
 
005 (999) OTHER
(CELLAR) FUSES NOT INSTALLED AS PER ADVISORY BOARD DRAWINGS
RSLV 07/18/2016 07/18/2016 01/30/2017