Electrical Application Details for App #: A333411
Premises: 11-35 45 AVENUE QUEENS BIN: 4000438     Block: 52   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 11-35 45 AV Census Tract:   7 Health Area:  0720
ROF. PEN. 001 THRU 006 Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    420828180
DOB Cross Street(s):    11 STREET,    21 STREET
Status:   C - JOB IS SIGNED OFF 06/08/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/21/2014 9:27 PM
Application Entered:   12/21/2014 Job Start Date:   12/22/2014
Last Change:   06/08/2016 Job End Date:   11/15/2015
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     06/02/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010902 Licensee Name: KWOK WAH TANG
Firm: 004115 Firm Name: E D ELECTRICAL INC
Firm Phone: 718-331-3887  Firm Address: 6614 14TH AVENUE BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $2,020.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  420828180
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GEORGE XU
Owner Business Name: MURRAY PARK NORTH LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  39  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  39  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    30  30  10  20             
002    50  150  24  40  60             
003    50  150  24  40  60             
004    50  150  24  40  60             
005    50  150  24  40  60             
006    50  150  24  40  60             
PEN    10               
ROF             
Buildings Total 288  792  123  216  328              
Total Units : 1753 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 39 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/21/2014 Notice: 1 - FIRST NOTICE 05/05/2016
Power Issued: 12/21/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A333411
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/04/2016 05/05/2016 ECH V (60) (15)
INSPECTION COMMENTS: APARTMENT 4C AND 2ND AND 3RD FLOOR NOT INSPECTED CONTRACTOR MUST INCLUDE MOTORS AND OTHER SERVICE SWITCHES ON APPLICATION
 
(2) 06/02/2016 06/02/2016 ECH C R (59) (0)
INSPECTION COMMENTS: UNDER CABINET LIGHTING HAS BEEN REMOVED. MOTORS ARE ON NEW APP. #A349780 AND CAN BE SIGNED OFF.

OBJECTION FOR APPLICATION #: A333411
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) PANELS MUST HAVE LEGIBLE DIRECTORIES
RSLV 05/04/2016 05/04/2016 06/02/2016
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) HOT WATER RECEPTACLE IN CLOSETS
RSLV 05/04/2016 05/04/2016 06/02/2016
 
003 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
(ALL FLOORS) LOAD CALCULATION REQUIRED 215.5
RSLV 05/04/2016 05/04/2016 06/02/2016
 
004 (999) OTHER
(ALL FLOORS) KO SEALS NOT CLOSED IN ALL 1ST FL AND ROOF PANELS
RSLV 05/04/2016 05/04/2016 06/02/2016
 
005 (999) OTHER
(ALL FLOORS)UNDER CABINET LIGHTING 120V AND DC SHARE BOX AND CONNECTOR, DC WIRENOT RATED FOR 120V - 300.3(C)
RSLV 05/04/2016 05/04/2016 06/02/2016
 
006 (999) OTHER
(ALL FLOORS)UNDER CABINET LIGHT DRIVER NOT INSTALLED PER SPEC. CORD IS CUT 110.3
RSLV 05/04/2016 05/04/2016 06/02/2016
 
007 (999) OTHER
(ALL FLOORS)ALL APARTMENT LAUNDRY CLOSETS LACK RECEPTACLES 210.52(F) (ARC-FAULTPROTECTION REQ.)
RSLV 05/04/2016 05/04/2016 06/02/2016
 
008 ( 29) OUTLET BOXES ARE NOT COVERED
(GROUND FLOOR) J-BOXES OPEN THROUGHOUT GROUND FLOOR
RSLV 05/04/2016 05/04/2016 06/02/2016
 
009 (999) OTHER
(GROUND FLOOR)FIRE PUMP SERVICE SWITCH FUSED HIGHER THAN 600% -- AMENDMENT 695.4
RSLV 05/04/2016 05/04/2016 06/02/2016
 
010 (999) OTHER
(GROUND FLOOR) TEMP WIRING HAS NOT BEEN REMOVED IN GARAGE 590.3
RSLV 05/04/2016 05/04/2016 06/02/2016
 
011 (999) OTHER
(GROUND FLOOR)COMMUNICATION WIRING NOT TO BE INSTALLED IN ELECTRICAL SERVICE ROOMAMENDMENT 800.133(D)
RSLV 05/04/2016 05/04/2016 06/02/2016
 
012 (999) OTHER
(GROUND FLOOR) FLUORESCENT LIGHTS DO NOT HAVE DISCONNECTS 410.130(G)
RSLV 05/04/2016 05/04/2016 06/02/2016
 
013 (999) OTHER
(GROUND FLOOR)EMT PASSES THROUGH FLUORESCENT LIGHT FIXTURES IN GARAGE 110.2
RSLV 05/04/2016 05/04/2016 06/02/2016
 
014 (999) OTHER
(GROUND FLOOR)LIGHT FIXTURES ON GROUND FLOOR LACK GROUND PATHWAY 250.4
RSLV 05/04/2016 05/04/2016 06/02/2016
 
015 ( 17) DEFECTIVE SWITCHES ARE IN USE
(ROOF) HEATER ROOM 3 WAY SWITCHES
RSLV 05/04/2016 05/04/2016 06/02/2016