| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER ROOF BALCONY 1ST FL BASEMENT OUTSIDE GFCI RECEPTACLES TR, WR RECEPTACLES NOT PROVIDED 406.11/406.8 |
RSLV |
07/27/2015 |
07/27/2015 |
09/16/2015 |
| |
| 002 |
(999) |
OTHER ROOF BALCONY, 1ST FL, BASEMENT OUTSIDE GFCI IN USE COVER NOT PROVIDED 406.8 |
RSLV |
07/27/2015 |
07/27/2015 |
09/16/2015 |
| |
| 003 |
(999) |
OTHER ALL APARTMENTS KITCHEN AND BATHROOM GFCI RECEPTACLE TR RECEPTACLES NOT 406.8 |
RSLV |
07/27/2015 |
09/16/2015 |
11/02/2015 |
| |
| 004 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED 2ND FL LEFT APT PANEL COMBO AFCI NOT PROVIDED |
RSLV |
07/27/2015 |
09/16/2015 |
11/02/2015 |
| |
| 005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX 2ND FL SUB PANELS |
RSLV |
07/27/2015 |
09/16/2015 |
11/02/2015 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 3RD FL JACUZZI RECEPTACLE |
RSLV |
07/27/2015 |
09/16/2015 |
11/02/2015 |
| |
| 007 |
( 53) |
GFCI HAS NOT BEEN PROVIDED 1ST FL KITCHEN PENINSULA RECEPTACLE |
RSLV |
07/27/2015 |
07/27/2015 |
09/16/2015 |