BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A331512
Premises: 32-15 35 STREET QUEENS BIN: 4009694     Block: 646   Lot: 30
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 3215 35 ST Census Tract:   59 Health Area:  0400
BOILER ROOM Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
DOB Cross Street(s):   BROADWAY,    34 AVENUE
Status:   C - JOB IS SIGNED OFF 02/04/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/17/2014 5:18 PM
Application Entered:   10/17/2014 Job Start Date:   10/19/2014
Last Change:   02/04/2016 Job End Date:   11/25/2014
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     12/23/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010102 Licensee Name: GEORGE HOLNESS
Firm: 002832 Firm Name: GEORGE HOLNESS
Firm Phone: 347-945-2512  Firm Address: 3870 WHITE PLAINS ROAD BRONX NY 10467 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $52.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN VELAZOUEZ
Owner Business Name: 3215 OWNERS CORP
Authorized Representative:  JOHN VELAZOUEZ
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  BOILER CONTROLERS

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001                     
Buildings Total                       
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/11/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING TO INDUSTRIAL COMBUSTION BOILER UNIT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A331512
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/22/2015 06/29/2015 TS1 N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 07/31/2015 08/11/2015 COB A (40) (1) Y
INSPECTION COMMENTS: OBJECTIONS
 
(3) 12/23/2015 12/23/2015 EVG C R (1) (0)
INSPECTION COMMENTS: VIOLATIONS REMOVED.

OBJECTION FOR APPLICATION #: A331512
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BASEMENT BOILER ROOM PANEL FEEDER GROUNDED NEUTRAL CONDUCTOR GREENGROUNDING CONDUCTOR USED AS NEUTRAL NOT PERMITTED 250.119
RSLV 07/31/2015 07/31/2015 12/23/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back