| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
400 |
| C. 201 Up to 600 AMPS |
1 |
600 |
| D. 601 Up to 1200 AMPS |
1 |
1,000 |
| E. Over 1200 AMPS |
3 |
(1) 3,000 (2) 4,000 |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
3/0 |
| D. Over 250 MCM |
49 |
(46) 350 (1) 1.6K(3) 2.5K |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
304 |
16/32 |
| C. 3 Phase Up to 225 AMPS |
35 |
30/54 |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 002)GENERATOR, FRAME OF GENERATOR TO BE GROUNDED TO WATER MAIN |
RSLV |
03/01/2016 |
03/01/2016 |
04/10/2016 |
| |
| 002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 026) ROOF, GFCI NOT PROVIDED |
RSLV |
03/01/2016 |
03/01/2016 |
04/10/2016 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (GROUND FLOOR) FIRE PUMP ROOM, FIRE PUMP, SEAL TIGHT NO GROUND |
RSLV |
03/01/2016 |
03/01/2016 |
04/10/2016 |
| |
| 004 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (GROUND FLOOR)SERVICE ROOM, 3RD DOOR NOT ON PRINT, COMMERCIAL METERS IN ONELOCATION AND RESIDENTAIL METERS RELOCATED |
RSLV |
03/01/2016 |
03/01/2016 |
04/10/2016 |
| |
| 005 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (GROUND FLOOR)SERVICE ROOM, FEED FROM FIRE PUMP SWITCH TO CONTROLLER VITALINK MCINSTALLED NOT ON PRINT |
RSLV |
03/01/2016 |
03/01/2016 |
04/10/2016 |
| |
| 006 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (GROUND FLOOR)SERVICE ROOM, FIRE ALARM FUSE CUT OUT, SINGLE PHASE, AND FED WITH#10 NOT PER DRAWING |
RSLV |
03/01/2016 |
03/01/2016 |
04/10/2016 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (GROUND FLOOR)SERVICE ROOM, FIRE PUMP METER PAN NOT PAINTED RED AS PER DRAWING |
RSLV |
03/01/2016 |
03/01/2016 |
04/10/2016 |