Electrical Application Details for App #: A329226
Premises: 54-05 SKILLMAN AVENUE QUEENS BIN: 4594818     Block: 1239   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 54-25 SKILLMAN AV Census Tract:   251 Health Area:  0920
BASEMENT 1ST AND 2ND Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11377 Community Board:   402
DOB Cross Street(s):    55 STREET,    56 STREET
Status:   C - JOB IS SIGNED OFF 05/02/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/07/2014 9:49 AM
Application Entered:   08/07/2014 Job Start Date:   08/07/2014
Last Change:   05/02/2017 Job End Date:   05/22/2015
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     05/02/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011268 Licensee Name: CHARLES DAMBROSE
Firm: 002818 Firm Name: STANCO SYSTEM ELEC'L CONT
Firm Phone: 718-761-7373  Firm Address: 4061 VICTORY BOULEVARD STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $187.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GORDON TUNG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 AMP
B. 101 Up to 200 AMPS  1  200 AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1 30 CKT AND 1 42 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  106    20                   
002  219    26                   
Buildings Total   46                      
Total Units : 46 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/25/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW MDF AND COMPUTER CLASSROOM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A329226
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/24/2017 04/25/2017 COB V (60) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 05/02/2017 05/02/2017 EVG C R (70) (0)
INSPECTION COMMENTS: JOB PASSED.

OBJECTION FOR APPLICATION #: A329226
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 001) MDF ROOM, RECEPTACLES NOT FASTEN TO BOX
RSLV 04/24/2017 04/24/2017 05/02/2017
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 001) MDF ROOM, RECEPTACLES MC GROUND NOT BONDED TO BOX
RSLV 04/24/2017 04/24/2017 05/02/2017
 
003 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 002)COMPUTER ROOM, RECEPTACLES EQUIPMENT IN WIRE MOULD NOT BONDED TOENCLOSURE
RSLV 04/24/2017 04/24/2017 05/02/2017