BIS Menu  |  DOB Violations  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A326043
Premises: 50-01 2 STREET QUEENS BIN: 4594739     Block: 16   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2-10 50 AV Census Tract:   1 Health Area:  0720
1FL Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
DOB Cross Street(s):    2 STREET,    5 STREET
Status:   C - JOB IS SIGNED OFF 01/24/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/14/2014 2:31 PM
Application Entered:   04/14/2014 Job Start Date:   04/14/2014
Last Change:   01/24/2017 Job End Date:   02/15/2015
Appointment Status:   
Last Inspection By:   FENTY, WAYNE       On     11/09/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011827 Licensee Name: JOSEPH P CANTALINO
Firm: 004046 Firm Name: RIGHTWAY ELECTRICAL INC
Firm Phone: 212-334-6918  Firm Address: 18 ORCHARD STREET, 1ST FL NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $142.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   COFFEE SHOP
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 50-01 2ND STREET ASSOC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1-100 AMP
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    20  25    10         
Buildings Total 20  25    10              
Total Units : 71 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/12/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A326043
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/08/2014 09/12/2014 TS1 V (30) (7) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 06/14/2015 06/26/2015 FWE P (15) (0) Y
INSPECTION COMMENTS: ONLY 22 REMOVED N/A TO PANEL
 
(3) 11/09/2016 11/14/2016 WYF C R (25) (0)
INSPECTION COMMENTS: ALL OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: A326043
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) PANEL CIRCUITS NOT GROUPED 210.4(D)
RSLV 09/08/2014 09/08/2014 11/09/2016
 
002 (999) OTHER
(ALL FLOORS)PANEL SUB PANEL CIRCUITS NEUTRAL NOT TERMINATED IN ITS PANEL 110.2
RSLV 09/08/2014 09/08/2014 11/09/2016
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)PANEL FIXED EQUIPMENT NOT PROPERLY GROUNDED OUTLET BOXES CEILING BOXES MC MUST BE BONDED TO BOX
RSLV 09/08/2014 09/08/2014 11/09/2016
 
004 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
(ALL FLOORS) LIGHTS LIGHTS FIXTURES NOT APPROVED (PENDANTS)
RSLV 09/08/2014 09/08/2014 11/09/2016
 
005 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(ALL FLOORS) PANEL CONDUCTORS NOT DERATED
RSLV 09/08/2014 09/08/2014 11/09/2016
 
006 (999) OTHER
(ALL FLOORS)TWO POLE BREAKERS NOT INSTALLED ON MULTIWIRE BRANCH CIRCUITS 210.4(B)
RSLV 09/08/2014 09/08/2014 11/09/2016
 
007 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) PANEL NO DIRECTORY
RSLV 09/08/2014 09/08/2014 11/09/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.