| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
1-100 AMP |
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS) PANEL CIRCUITS NOT GROUPED 210.4(D) |
RSLV |
09/08/2014 |
09/08/2014 |
11/09/2016 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS)PANEL SUB PANEL CIRCUITS NEUTRAL NOT TERMINATED IN ITS PANEL 110.2 |
RSLV |
09/08/2014 |
09/08/2014 |
11/09/2016 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS)PANEL FIXED EQUIPMENT NOT PROPERLY GROUNDED OUTLET BOXES CEILING BOXES MC MUST BE BONDED TO BOX |
RSLV |
09/08/2014 |
09/08/2014 |
11/09/2016 |
| |
| 004 |
( 28) |
ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED (ALL FLOORS) LIGHTS LIGHTS FIXTURES NOT APPROVED (PENDANTS) |
RSLV |
09/08/2014 |
09/08/2014 |
11/09/2016 |
| |
| 005 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED (ALL FLOORS) PANEL CONDUCTORS NOT DERATED |
RSLV |
09/08/2014 |
09/08/2014 |
11/09/2016 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)TWO POLE BREAKERS NOT INSTALLED ON MULTIWIRE BRANCH CIRCUITS 210.4(B) |
RSLV |
09/08/2014 |
09/08/2014 |
11/09/2016 |
| |
| 007 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) PANEL NO DIRECTORY |
RSLV |
09/08/2014 |
09/08/2014 |
11/09/2016 |