| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
1 |
1600 AMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
1 SET OF # 2 |
| C. Over 1/0 to 250 MCM |
1 |
1 SET OF 3/0 |
| D. Over 250 MCM |
4 |
4 SETS OF 500M CM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
28 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
100 AMP |
| D. 3 Phase Over 225 AMPS |
1 |
200 AMP |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(265) |
HIGH LEG NOT PROPERLY IDENTIFIED/INSTALLED (BASEMENT) FIRE PUMP DISCONNECT SWITCH NOT PAINTED FULLY RED. |
RSLV |
03/11/2016 |
03/11/2016 |
05/03/2016 |
| |
| 002 |
(999) |
OTHER (BASEMENT) FIRE PUMP CONTROLLER NOT IN PLACE. |
RSLV |
03/11/2016 |
03/11/2016 |
05/03/2016 |
| |
| 003 |
(999) |
OTHER (FLOOR: 001)314.19 THROUGHOUT THE ENTIRE BUILDING ALL MICROWAVE RECEPTACLEPLACED IN CABINETS NEED EXTENSION COLLARS |
RSLV |
05/03/2016 |
05/03/2016 |
05/16/2016 |
| |
| 004 |
(999) |
OTHER (FLOOR: 001) LOBBY WALL SCONCES NEED TO BE GROUNDED. |
RSLV |
05/03/2016 |
05/03/2016 |
05/16/2016 |
| |
| 005 |
(999) |
OTHER (FLOOR: 001) 314.19 RECEPTACLES ON TERRACES NEED EXTENSION COLLARS. |
RSLV |
05/03/2016 |
05/03/2016 |
05/16/2016 |
| |
| 006 |
(999) |
OTHER (FLOOR: 001)406.8 RECEPTACLES ON SOME OF TERRACES NEED IN USE COVERS. |
RSLV |
05/03/2016 |
05/03/2016 |
06/22/2016 |
| |
| 007 |
(999) |
OTHER (CELLAR)CELLAR END LINE BOX 2 SETS OF 3/0 CABLES TERMINATED BACK TO BACK ANDARE NOT A PARALLEL SET. |
RSLV |
05/03/2016 |
05/03/2016 |
05/16/2016 |
| |
| 008 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 007)APTS 701, 702, 703, KITCHEN COUNTERTOP, MISSING GFCI RECEPTACLES |
RSLV |
05/16/2016 |
05/16/2016 |
06/22/2016 |
| |
| 009 |
( 44) |
INSTALL. NOT CONFORM WITH REQUIREMENTS FOR CLASSIFIED LOCATION (ALL FLOORS)AL APTS, MICROWAVE OUTLETS, SHEETROCK SCREWS USED TO FASTENRECEPTACLES |
RSLV |
05/16/2016 |
05/16/2016 |
06/22/2016 |
| |
| 010 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (CELLAR) SERVICE ROOM, FIRE ALARM FUSE CUT OUT, NEUTRAL NOT BONDED |
RSLV |
05/16/2016 |
05/16/2016 |
06/22/2016 |