Electrical Application Details for App #: A324870
Premises: 28-18 ASTORIA BOULEVARD QUEENS BIN: 4617229     Block: 596   Lot: 45
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 28-18 ASTORIA BLVD Census Tract:   69 Health Area:  0300
CEL, BSMT, 1ST-7TH FLRS, ROOF Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
Related Job Number:    402604669
DOB Cross Street(s):    28 STREET,    29 STREET
Status:   C - JOB IS SIGNED OFF 07/15/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/03/2014 3:34 PM
Application Entered:   03/03/2014 Job Start Date:   03/03/2014
Last Change:   07/15/2016 Job End Date:   02/28/2015
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     06/22/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012072 Licensee Name: CLINTON COURTNEY
Firm: 003770 Firm Name: TRINCITY ELECTRIC, INC
Firm Phone: 718-712-4300  Firm Address: 224-17 MERRICK BLVD SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $1,846.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   ELEVATOR APT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHARALBOS BAKALIS
Owner Business Name: 25-87/89 37TH ST LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  1600 AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  1 SET OF # 2
C. Over 1/0 to 250 MCM  1  1 SET OF 3/0
D. Over 250 MCM  4  4 SETS OF 500M CM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  28  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  100 AMP
D. 3 Phase Over 225 AMPS  1  200 AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  CEL  34  10    10               
BAS  BSMT  10                   
001  1FL  56  84  17               
002  2FL  59  79  19               
003  3FL  59  79  19               
004  4FL  53  79  19               
005  5FL  56  73  17               
006  6FL  56  73  17               
007  7FL  55  70  19               
ROF  ROOF                   
Buildings Total 444  552  24  137                  
Total Units : 1157 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 28 #4-Wire 2 #10-Wire 1
Existing Meters 0 + New Meters 31 - Removed Meters 0 = Total Meters 31

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/03/2014 Notice: 1 - FIRST NOTICE 05/16/2016
Power Issued: 03/03/2014 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A324870
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/11/2016 03/14/2016 EVG V (49) (2)
INSPECTION COMMENTS: JOB FAILED, FIRE PUMP CONTROLLER HAS BEEN DISCONNECTED AND IS NOT IN PLACE. NEED MORE TIME TO INSPECT THE REST OF THE JOB.
 
(2) 05/03/2016 05/03/2016 EVG V R (118) (5)
INSPECTION COMMENTS: JOB FAILED. ELEVATOR NEEDS TO BE INSPECTED.
 
(3) 05/16/2016 05/16/2016 COB V Y (57) (3)
INSPECTION COMMENTS: ADDITIONAL OBJECTIONS ISSUED
 
(4) 06/22/2016 06/22/2016 DNM C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: A324870
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (265) HIGH LEG NOT PROPERLY IDENTIFIED/INSTALLED
(BASEMENT) FIRE PUMP DISCONNECT SWITCH NOT PAINTED FULLY RED.
RSLV 03/11/2016 03/11/2016 05/03/2016
 
002 (999) OTHER
(BASEMENT) FIRE PUMP CONTROLLER NOT IN PLACE.
RSLV 03/11/2016 03/11/2016 05/03/2016
 
003 (999) OTHER
(FLOOR: 001)314.19 THROUGHOUT THE ENTIRE BUILDING ALL MICROWAVE RECEPTACLEPLACED IN CABINETS NEED EXTENSION COLLARS
RSLV 05/03/2016 05/03/2016 05/16/2016
 
004 (999) OTHER
(FLOOR: 001) LOBBY WALL SCONCES NEED TO BE GROUNDED.
RSLV 05/03/2016 05/03/2016 05/16/2016
 
005 (999) OTHER
(FLOOR: 001) 314.19 RECEPTACLES ON TERRACES NEED EXTENSION COLLARS.
RSLV 05/03/2016 05/03/2016 05/16/2016
 
006 (999) OTHER
(FLOOR: 001)406.8 RECEPTACLES ON SOME OF TERRACES NEED IN USE COVERS.
RSLV 05/03/2016 05/03/2016 06/22/2016
 
007 (999) OTHER
(CELLAR)CELLAR END LINE BOX 2 SETS OF 3/0 CABLES TERMINATED BACK TO BACK ANDARE NOT A PARALLEL SET.
RSLV 05/03/2016 05/03/2016 05/16/2016
 
008 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 007)APTS 701, 702, 703, KITCHEN COUNTERTOP, MISSING GFCI RECEPTACLES
RSLV 05/16/2016 05/16/2016 06/22/2016
 
009 ( 44) INSTALL. NOT CONFORM WITH REQUIREMENTS FOR CLASSIFIED LOCATION
(ALL FLOORS)AL APTS, MICROWAVE OUTLETS, SHEETROCK SCREWS USED TO FASTENRECEPTACLES
RSLV 05/16/2016 05/16/2016 06/22/2016
 
010 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(CELLAR) SERVICE ROOM, FIRE ALARM FUSE CUT OUT, NEUTRAL NOT BONDED
RSLV 05/16/2016 05/16/2016 06/22/2016