BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A324760
Premises: 232 BEACH 100 STREET QUEENS BIN: 4616237     Block: 16155   Lot: 15
   
Application Completed and Certified

Filed: 232 BEACH 100 ST Census Tract:   942.01 Health Area:  3700
1-3 Admin Area:   A - QUEENS Inspection Area:   M
QUEENS, NY 11694 Community Board:   414
Related Job Number:    402431980
DOB Cross Street(s):   STEEPLECHASE COURT,    DEAD END
Status:   C - JOB IS SIGNED OFF 10/13/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/26/2014 10:19 AM
Application Entered:   02/26/2014 Job Start Date:   02/26/2014
Last Change:   10/13/2015 Job End Date:   02/26/2015
Appointment Status:   
Last Inspection By:   POMERICO, RAYMOND E       On     10/06/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012580 Licensee Name: ANTHONY D LOMANTO
Firm: 004401 Firm Name: GENESIS ELECTRICAL GROUP
Firm Phone: 718-460-0263  Firm Address: 102-30 CORONA AVENUE CORP CORONA NY 11368 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $105.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRYAN WETHERALL
Owner Business Name: WETHERALL CONTRACTING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  17  29  16  17             
002  18  34  16  18             
003  21  34  20  21             
Buildings Total 56  97  11  52  56                
Total Units : 272 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/02/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  SERVICE, METERS, PANELS DONE BY OTHERS AS WELL AS ROUGH WIRING. WE ARE CHECKING AND COMPLETING ALL INTERIOR WORK

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A324760
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/26/2015 07/02/2015 RYP A (35) (4) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 10/06/2015 10/13/2015 RYP C R (15) (0) Y
INSPECTION COMMENTS: CERTIFICATE. PICKS UP APPLICATION A304832

OBJECTION FOR APPLICATION #: A324760
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
T/OUT BATHROOM RECEPTACLES REQUIRE INDIVIDUAL CIRCUITS 210.11C
RSLV 06/26/2015 06/26/2015 10/06/2015
 
002 (999) OTHER
1ST GROUNDING ELECTRODE CONDUCTOR TO COLD WATER MAIN REQUIRED 250.24(A)1 250.50
RSLV 06/26/2015 06/26/2015 10/06/2015
 
003 (999) OTHER
1ST SUPPLEMENTAL GROUNDING ELECTRODE NOT ACCESSIBLE 250.53
RSLV 06/26/2015 06/26/2015 10/06/2015
 
004 (999) OTHER
3RD FLOOR BALCONY RECEPTALCE NEED TO BE WR 406.8
RSLV 06/26/2015 06/26/2015 10/06/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back