Premises: 38-01 31 AVENUE QUEENS BIN: 4010626     Block: 660   Lot: 4
   
Application Completed and Certified

Filed: 3801 31 AV Census Tract:   155 Health Area:  0520
1ST FLOOR Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11103 Community Board:   401
DOB Cross Street(s):    38 STREET,    STEINWAY STREET
Status:   C - JOB IS SIGNED OFF 10/07/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/28/2014 10:20 PM
Application Entered:   01/28/2014 Job Start Date:   01/29/2014
Last Change:   10/07/2014 Job End Date:   05/20/2014
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     10/01/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010443 Licensee Name: CARDINAL HESCOTT
Firm: 000858 Firm Name: LEKTRIC INSTALLATIONS COR
Firm Phone: 718-469-3200  Firm Address: 3802 CHURCH AVENUE BROOKLYN NY 11203 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $171.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: POINT BRAZIL RESTAURANT
Authorized Representative:  ELZIE RIBEIRO
Relationship To Owner:   LEASE HOLDER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1 200A 42 CIRCUIT PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    59  26  11  59             
Buildings Total 59  26  11  59                
Total Units : 157 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/17/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A324132
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/28/2014 08/04/2014 TS1 N (20) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(2) 08/08/2014 08/14/2014 DEX A (50) (5) Y
INSPECTION COMMENTS: VIOLATIONS
 
(3) 09/04/2014 09/08/2014 TSO A R (30) (5) Y
INSPECTION COMMENTS: VIOLATIONS
 
(4) 09/15/2014 09/17/2014 TSO A R (35) (4) Y
INSPECTION COMMENTS: VIOLATIONS
 
(5) 10/01/2014 10/07/2014 TSO C R (50) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A324132
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ALL FRYERS COOKING AREA CONDUIT RUN UNDER HOOD 410.4C
RSLV 08/08/2014 08/08/2014 09/04/2014
 
002 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
BASEMENT FREEZERS POWER CONDUITS EMT CONNECTORS NOT APPROVED
RSLV 08/08/2014 08/08/2014 09/04/2014
 
003 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT FREEZERS WIRES FEEDING FROM DISCONNECT SWITCH TO FANS INSIDE FREEZER NO NIPPLE INSTALL FOR WIRE PROTECTION
RSLV 08/08/2014 08/08/2014 09/04/2014
 
004 ( 19) DEFECTIVE WIRING IS IN USE
1ST FLOOR OPEN GROUND OUTLETS FRONT OF RESTURANT SITTING AREA
RSLV 08/08/2014 08/08/2014 09/04/2014
 
005 ( 29) OUTLET BOXES ARE NOT COVERED
BASEMENT WATER METER ROOM MISSING PLATE FOR SWITCH
RSLV 08/08/2014 08/08/2014 09/04/2014
 
006 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
BASEMENT FREEZERS POWER CONDUITS EMT CONNECTORS NOT APPROVED
RSLV 09/04/2014 09/04/2014 09/15/2014
 
007 ( 19) DEFECTIVE WIRING IS IN USE
DISCONNECT SWITCH TO FANS INSIDE FREEZER NO NIPPLE INSTALL FOR WIRE PROTECTION
RSLV 09/04/2014 09/04/2014 09/15/2014
 
008 (999) OTHER
BASEMENT RACEWAY NOT CONTINOUS BACK OF TIME CLOCK 300.10
RSLV 09/04/2014 09/04/2014 09/15/2014
 
009 (999) OTHER
BASEMENT AC CONNECTORS USED FOR MC THROUGHOUT
RSLV 09/04/2014 09/04/2014 09/15/2014
 
010 (999) OTHER
NO SEAL RACEWAY DIFFERENT TEMP WALK IN BOX 300.7
RSLV 09/04/2014 09/04/2014 09/15/2014
 
011 (999) OTHER
BASEMENT AC CONNECTORS USED FOR MC THROUGHOUT
RSLV 09/15/2014 09/15/2014 10/01/2014
 
012 (999) OTHER
NO SEAL RACEWAY DIFFERENT TEMP WALK IN BOX 300.7
RSLV 09/15/2014 09/15/2014 10/01/2014
 
013 (999) OTHER
CELLAR NO BUSHING AC CABLE 320.40
RSLV 09/15/2014 09/15/2014 10/01/2014
 
014 (999) OTHER
CELLAR AC CONNECTORS USED FOR MC T/OUT 330.40
RSLV 09/15/2014 09/15/2014 10/01/2014