BIS Menu  |  Applications  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A323649
Premises: 319 BEACH 98 STREET QUEENS BIN: 4445407     Block: 16155   Lot: 21
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 320 BEACH 100 ST Census Tract:   942.01 Health Area:  3700
SERVICE WORK Admin Area:   A - QUEENS Inspection Area:   M
QUEENS, NY 11694 Community Board:   414
DOB Cross Street(s):   CROSS BAY VET MEMORIAL BRIDGE ET,    BEACH 100 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/09/2014 8:32 AM
Application Entered:   01/09/2014 Job Start Date:   01/10/2014
Last Change:   08/22/2025 Job End Date:   07/01/2014
Appointment Status:   
Last Inspection By:   POMERICO, RAYMOND E       On     06/01/2015      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012301 Licensee Name: AARON LEBOVITS
Firm: 004070 Firm Name: METRO ELEC'L CONTRS, INC
Firm Phone: 718-439-7466  Firm Address: 218 HAMILTON AVENUNE BROOKLYN NY 11231 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
012302 WEBER, MAYER 004070 METRO ELEC'L CONTRS, INC

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $0.00
Hurricane Sandy Damage:   Yes
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: GEMSTAR CONST
Authorized Representative:  Y SCHWARTZ
Relationship To Owner:   CONT.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  2-2500A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  13  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  4  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 01/09/2014 Notice: 1 - FIRST NOTICE 06/08/2015
Power Issued: 01/09/2014 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A323649
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/08/2015 01/13/2015 COB J G (50) (0) Y
INSPECTION COMMENTS: PANIC BARS NOT ON SERVICE ROOM DOORS. AWAITING ADVISORY BOARD APPROVED DRAWINGS
 
(2) 04/24/2015 04/29/2015 COB A G (15) (2) Y
INSPECTION COMMENTS: VIOLATIONS
 
(3) 05/15/2015 05/20/2015 RYP Z (0) (0) Y
INSPECTION COMMENTS: NOT INSPECTED
 
(4) 06/01/2015 06/08/2015 RYP A R E (65) (2) Y
INSPECTION COMMENTS: VIOLATIONS

OBJECTION FOR APPLICATION #: A323649
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BASEMENT SERVICE ROOM 1-2500A AND 1-1600A SERVICE SWITCHES INSTALLED
RSLV 04/24/2015 04/24/2015 06/01/2015
 
002 (999) OTHER
BASEMENT SERVICE ROOM DOORS FOR EQUIPMENT OVER 1200A SHALL OPEN IN DIRECTION OF EGRESS AND EQUIPPED WITH PANIC BAR 110.26.C.2
RSLV 04/24/2015 04/24/2015 06/01/2015
 
003 (999) OTHER
BASEMENT ARC FLASH WARNING LABELS REQUIRED 110.16
OPEN 06/01/2015 06/01/2015
 
004 (999) OTHER
BASEMENT PANEL SCHEDULES REQUIRED 408.4
OPEN 06/01/2015 06/01/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.