| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
2 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
2 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
13 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
|
| D. 3 Phase Over 225 AMPS |
4 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BASEMENT SERVICE ROOM 1-2500A AND 1-1600A SERVICE SWITCHES INSTALLED |
RSLV |
04/24/2015 |
04/24/2015 |
06/01/2015 |
| |
| 002 |
(999) |
OTHER BASEMENT SERVICE ROOM DOORS EQUIPMENT OVER 1200A SHALL OPEN IN DIRECTION OF EGRESS AND EQUIPPED WITH PANIC BARS |
RSLV |
04/24/2015 |
04/24/2015 |
06/01/2015 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BASEMENT SERVICE ENCLOSURE BOTTOM LESS ENCLOSURE BONDING TO BE 12 1/2 PERCENT OF NINE SETS 600 MCM 110.26C.2 |
RSLV |
04/24/2015 |
04/24/2015 |
06/01/2015 |
| |
| 004 |
(999) |
OTHER BASEMENT PANEL SCHEDULES REQUIRED 408.4 |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 005 |
(999) |
OTHER BASEMENT ARC FLASH WARNING LABELS REQUIRED 110.16 |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 006 |
(999) |
OTHER 999BASEMENT PANEL SCHDULES REQURIED 408.4 |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 007 |
(999) |
OTHER BASEMENT ARC FLASH WARNING LABELS REQUIRED 110.16 |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 008 |
(999) |
OTHER BASEMENT 1600A, SECOND FUSING SECTIONS DO NOT MATCH APPROVED DRAWING AMEND 110.2(B) |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 009 |
(999) |
OTHER BSMT BONDING JUMPERS UNDERSIZED 1600A SWITCH 250.102(D) |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 010 |
(999) |
OTHER BSMT DIRE PUMP FEED INSTALLED IN WRONG SECTION AS PER APPROVED DRAWING AMEND 110.2(B) |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 011 |
(999) |
OTHER BSMT SERVICE ENTRANCE CONDUCTORS NOT AS PER APPROVED DRAWING AMEND 110.2B |
OPEN |
06/01/2015 |
06/01/2015 |
|
| |
| 012 |
(999) |
OTHER BSMT SERVICE ENTRANCE NOT SUFFICIENT AS PER AMEND 230.42(A)2 |
OPEN |
06/01/2015 |
06/01/2015 |
|