BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A323620
Premises: 56-11 94 STREET QUEENS BIN: 4047078     Block: 1902   Lot: 39
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 56-11 94 ST Census Tract:   683 Health Area:  1910
SIDEWALK Admin Area:   A - QUEENS Inspection Area:   D
QUEENS, NY 11373 Community Board:   404
DOB Cross Street(s):    56 AVENUE,    57 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/08/2014 6:22 AM
Application Entered:   01/08/2014 Job Start Date:   01/08/2014
Last Change:   08/22/2025 Job End Date:   01/08/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   MICHAEL BENISCHEK       On     08/07/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010285 Licensee Name: GREGORY PAPANTONIOU
Firm: 003867 Firm Name: BOROWIDE ELECT'L CONTR'S
Firm Phone: 718-204-1347  Firm Address: 36-07 20TH AVENUE INC ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
W - SIDEWALK SHED WIRING & LIGHTING
Total Fee:  $41.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: EVEREST SCAFFOLDING
Authorized Representative:  JIMMY DOWNES
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SWK          15             
Buildings Total       15                
Total Units : 16 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 08/07/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  TEMPORARY SHED LIGHTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A323620
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/20/2015 02/24/2015 DEX J (15) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS. NO COMMENTS
 
(2) 08/07/2017 08/07/2017 MBE V (15) (3)
INSPECTION COMMENTS: OBJECTIONS ISSUED.

OBJECTION FOR APPLICATION #: A323620
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (143) LUMINAIRES NOT PROPERLY SUPPORTED/SECURED
(OPEN SPACE)LIGHTING FIXTURES ARE NOT SECURED / FASTENED. ARTICLE # 410.30
OPEN 08/07/2017 08/07/2017
 
002 (239) GFCI HAS NOT BEEN PROVIDED
(OPEN SPACE)GFCI PROTECTION IS NOT PROVIDED FOR SHED LIGHTING. ARTICLE # 590.6
OPEN 08/07/2017 08/07/2017
 
003 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(OPEN SPACE)CONDUIT IS NOT SUPPORTED EVERY 10' FRONT & SIDE OF BUILDING. ARTICLE# 342.30
OPEN 08/07/2017 08/07/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order