BIS Menu  |  Certs. Occupancy  |  Application Data  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A323109
Premises: 37-76 62 STREET QUEENS BIN: 4027860     Block: 1216   Lot: 83
   
Application Completed and Certified

Filed: 37-76 62 ST Census Tract:   261 Health Area:  1021
BASEMENT Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11377 Community Board:   402
DOB Cross Street(s):    37 AVENUE,    39 AVENUE
Status:   C - JOB IS SIGNED OFF 04/06/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/11/2013 9:07 AM
Application Entered:   12/11/2013 Job Start Date:   12/11/2013
Last Change:   04/06/2015 Job End Date:   04/11/2014
Appointment Status:   
Last Inspection By:   SAMARAS TASOS       On     03/18/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010285 Licensee Name: GREGORY PAPANTONIOU
Firm: 003867 Firm Name: BOROWIDE ELECT'L CONTR'S
Firm Phone: 718-204-1347  Firm Address: 36-07 20TH AVENUE INC ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,635.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN KAPETANOS
Owner Business Name: DARBY REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  39  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  39  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
Buildings Total                       
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 39 #4-Wire 1 #10-Wire 0
Existing Meters 40 + New Meters 39 - Removed Meters 39 = Total Meters 40

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/11/2013 Notice: 1 - FIRST NOTICE 02/19/2015
Power Issued: 12/11/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADE SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A323109
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/13/2015 02/19/2015 DEX V E (60) (3) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 03/18/2015 03/25/2015 TS1 C R E (90) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A323109
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
NEED LOAD CALCULATION FOR (40) APARTMENT (100AMP) FROM 600 AMP SERVICE SWITCH
RSLV 02/13/2015 02/13/2015 03/18/2015
 
002 (279) WATER METER JUMPER IS MISSING/IMPROPER
BASEMENT NO JUMPER FOR WATER METER INSTALLED
RSLV 02/13/2015 02/13/2015 03/18/2015
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
THROUGHOUT APARTMENT THROUGHOUT 14 AMP WIRE FUSED 20 AMPS BREAKER
RSLV 02/13/2015 02/13/2015 03/18/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Certs. Occupancy  |  Application Data  |  Electrical Inspection Work Order  |  Back