BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A322555
Premises: 43-12 SKILLMAN AVENUE QUEENS BIN: 4001765     Block: 158   Lot: 24
   
Application Completed and Certified

Filed: 4312 SKILLMAN AV Census Tract:   183 Health Area:  0910
BASE,1ST & 2ND FLOORS Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11104 Community Board:   402
DOB Cross Street(s):    43 STREET,    44 STREET
Status:   C - JOB IS SIGNED OFF 03/31/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/18/2013 3:03 PM
Application Entered:   11/18/2013 Job Start Date:   11/20/2013
Last Change:   03/31/2014 Job End Date:   12/30/2013
Appointment Status:   
Last Inspection By:   SAMARAS TASOS       On     03/24/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009860 Licensee Name: JOSEPH TODARO
Firm: 002632 Firm Name: TNT ELECTRIC CO., INC.
Firm Phone: 347-763-2342  Firm Address: 41 BOX STREET, STE 301 BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $72.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH L DELPH
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  20             
001  10  25  10             
002  20             
Buildings Total 25  65  18  25                
Total Units : 138 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/24/2014
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  BASE,1ST & 2ND FLOORS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A322555
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/19/2014 02/24/2014 TS1 A (30) (4) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 03/24/2014 03/31/2014 TS1 C R (30) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A322555
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
A/C ALL AIR CONDITION RECEPTACLES SHALL BE AT SINGLE TYPE NOT DUPLEX
RSLV 02/19/2014 02/19/2014 03/24/2014
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
PANELS NO AFCI PROTECTION PROVIDED FOR A/C CIRCUITS
RSLV 02/19/2014 02/19/2014 03/24/2014
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
KITCHEN COUNTERTOP GREATER THAN 12" REQUIRE GFCI
RSLV 02/19/2014 02/19/2014 03/24/2014
 
004 (999) OTHER
2ND FLOOR HALLWAY RECEPTACLE NOT PROVIDED WALLS GREATER THAN OREQUAL TO 10FT REQUIRE RECEPTACLE 210.52(H)
RSLV 02/19/2014 02/19/2014 03/24/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.