| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400 AMP |
| D. 601 Up to 1200 AMPS |
2 |
2 - 800 AMP |
| E. Over 1200 AMPS |
1 |
2000 AMP |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
93 |
|
| B. Over #2 to 1/0 |
11 |
|
| C. Over 1/0 to 250 MCM |
2 |
|
| D. Over 250 MCM |
9 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
98 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
6 |
|
| D. 3 Phase Over 225 AMPS |
3 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER BASEMENT NEUTRAL DISCONNECT LINK NOT AS PER DWG 110.3 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 002 |
(999) |
OTHER BASEMENT T-OUT FUSES NOT AS PER DWG 110.3 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 003 |
(999) |
OTHER BASEMENT EGC F.P. SS. TOO SMALL 250.122 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 004 |
(999) |
OTHER BASEMENT FUSES HDP NOT AS DWG 110.3 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 005 |
(999) |
OTHER BASEMENT OCP ELEVATOR DISCO BASEMENT TOO LARGE 310.16 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 006 |
(999) |
OTHER BASEMENT MTR ROOM MULTIMOTOR ELEVATOR FEEDER AND TAP OCP NEED SELECTIVE COORDINATION 620.62 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 007 |
(999) |
OTHER F.P ROOM EGC F.P. FROM CONTROLLER TOO SMALL 250.122 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 008 |
(999) |
OTHER T-OUT NO ARC FLASH WARNING LABELS 110.16 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 009 |
( 19) |
DEFECTIVE WIRING IS IN USE ROOF NEURAL NOT CONNECTED GENERATOR |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 010 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE ROOF NO BUSHING GENERATOR LFMC |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 011 |
(999) |
OTHER ROOF OPEN CONDUCTORS BACK EXIT SIGNS ROOF 300.3 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 012 |
(999) |
OTHER ROOF OCP MAKEUP AIR ROOF TOO LARGE 110.3 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |
| |
| 013 |
(999) |
OTHER GND FL OUTSIDE BX OUTSIDE BACK EXIT SIGN GROUND FLOOR 314.15 |
RSLV |
07/28/2014 |
07/28/2014 |
09/12/2014 |