BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A320227
Premises: 26-10 JACKSON AVENUE QUEENS BIN: 4307182     Block: 268   Lot: 15
   
Application Completed and Certified

Filed: 26-14 JACKSON AV Census Tract:   19
CELLAR,1-14,ROOF Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    420603047
DOB Cross Street(s):    44 DRIVE,    PURVES STREET
Status:   C - JOB IS SIGNED OFF 09/23/2014
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   08/23/2013 Job Start Date:   02/14/2013
Last Change:   09/23/2014 Job End Date:   02/14/2015
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     09/12/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010720 Licensee Name: ROBERT GIOELLO
Firm: 004157 Firm Name: GLO ELECTRIC LLC
Firm Phone: 718-761-4323  Firm Address: 441 WILD AVENUE, 2ND FLOOR STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  420603047
Building Used As:   Z - Commercial/Residential (1  Stores, 98 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   51749     Submittal #: 13A0117  
Owner / Occup: SANDY LOWENTHIEL
Owner Business Name: L & M BUILDERS
Authorized Representative:  ROBERT GIOELLO
Relationship To Owner:   AUTHORIZED REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMP
D. 601 Up to 1200 AMPS  2  2 - 800 AMP
E. Over 1200 AMPS  1  2000 AMP
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  93  
B. Over #2 to 1/0  11  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  9  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  98  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  
D. 3 Phase Over 225 AMPS  3  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 1031  2290    630  1031     85           
Total Units : 5067 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 98 #4-Wire 3 #10-Wire 1
Existing Meters 0 + New Meters 102 - Removed Meters 0 = Total Meters 102

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/23/2013 Notice: 1 - FIRST NOTICE 08/01/2014
Power Issued: 08/23/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A320227
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/28/2014 08/01/2014 TSO A E (140) (13) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 09/12/2014 09/16/2014 TSO C R E (65) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A320227
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT NEUTRAL DISCONNECT LINK NOT AS PER DWG 110.3
RSLV 07/28/2014 07/28/2014 09/12/2014
 
002 (999) OTHER
BASEMENT T-OUT FUSES NOT AS PER DWG 110.3
RSLV 07/28/2014 07/28/2014 09/12/2014
 
003 (999) OTHER
BASEMENT EGC F.P. SS. TOO SMALL 250.122
RSLV 07/28/2014 07/28/2014 09/12/2014
 
004 (999) OTHER
BASEMENT FUSES HDP NOT AS DWG 110.3
RSLV 07/28/2014 07/28/2014 09/12/2014
 
005 (999) OTHER
BASEMENT OCP ELEVATOR DISCO BASEMENT TOO LARGE 310.16
RSLV 07/28/2014 07/28/2014 09/12/2014
 
006 (999) OTHER
BASEMENT MTR ROOM MULTIMOTOR ELEVATOR FEEDER AND TAP OCP NEED SELECTIVE COORDINATION 620.62
RSLV 07/28/2014 07/28/2014 09/12/2014
 
007 (999) OTHER
F.P ROOM EGC F.P. FROM CONTROLLER TOO SMALL 250.122
RSLV 07/28/2014 07/28/2014 09/12/2014
 
008 (999) OTHER
T-OUT NO ARC FLASH WARNING LABELS 110.16
RSLV 07/28/2014 07/28/2014 09/12/2014
 
009 ( 19) DEFECTIVE WIRING IS IN USE
ROOF NEURAL NOT CONNECTED GENERATOR
RSLV 07/28/2014 07/28/2014 09/12/2014
 
010 ( 42) BUSHINGS ARE MISSING OR LOOSE
ROOF NO BUSHING GENERATOR LFMC
RSLV 07/28/2014 07/28/2014 09/12/2014
 
011 (999) OTHER
ROOF OPEN CONDUCTORS BACK EXIT SIGNS ROOF 300.3
RSLV 07/28/2014 07/28/2014 09/12/2014
 
012 (999) OTHER
ROOF OCP MAKEUP AIR ROOF TOO LARGE 110.3
RSLV 07/28/2014 07/28/2014 09/12/2014
 
013 (999) OTHER
GND FL OUTSIDE BX OUTSIDE BACK EXIT SIGN GROUND FLOOR 314.15
RSLV 07/28/2014 07/28/2014 09/12/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order