| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
3 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
3 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
15 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER BASEMENT 400A SERVICE SWITCH TOP MIGB MISSING BONDING SCREW |
RSLV |
09/17/2014 |
09/17/2014 |
10/01/2014 |
| |
| 002 |
(999) |
OTHER BASEMENT 400A SERVICE SWITCH TOP LOCK RING & ENDLINE BOX RUSTED110.12 (B) |
RSLV |
09/17/2014 |
09/17/2014 |
10/01/2014 |
| |
| 003 |
(999) |
OTHER BASEMENT METER ENCLOSURES AND TERMINAL BOX 400A BUSES NOT TORQUED110.3B |
RSLV |
09/17/2014 |
09/17/2014 |
10/01/2014 |
| |
| 004 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE BASEMENT ELECTRICAL ROOM GFCI |
RSLV |
09/17/2014 |
09/17/2014 |
10/01/2014 |
| |
| 005 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER BASEMENT (2) 200A DISCONNECT TROUGH MIGB BONDING SCREW MISSING |
RSLV |
09/17/2014 |
09/17/2014 |
10/01/2014 |
| |
| 006 |
(999) |
OTHER KITCHEN. KITCHEN LIGHTS AND GFCI ON SAME CIRCUIT. MUST BE SEPERATE 210.52(B)(2) |
RSLV |
10/01/2014 |
10/01/2014 |
10/27/2014 |
| |
| 007 |
(999) |
OTHER BASEMENT. BASEMENT DISCONNECT SWITCH NO CLEARANCE PROVIDED 110.26 |
RSLV |
10/01/2014 |
10/01/2014 |
10/27/2014 |
| |
| 008 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ROOF FIXED EQUIPMENT (SEIMENS CONTROLLER) NOT GROUNDED |
RSLV |
10/01/2014 |
10/01/2014 |
10/27/2014 |