BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A312566
Premises: 14-57 BROADWAY QUEENS BIN: 4005792     Block: 531   Lot: 1
   
Application Completed and Certified

Filed: 1457 BROADWAY Census Tract:   77 Health Area:  0300
2ND FL. & STORE Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
DOB Cross Street(s):    14 STREET,    21 STREET
Status:   C - JOB IS SIGNED OFF 06/03/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/02/2013 3:00 PM
Application Entered:   02/02/2013 Job Start Date:   02/04/2013
Last Change:   06/03/2015 Job End Date:   02/04/2014
Appointment Status:   
Last Inspection By:   SAMARAS TASOS       On     05/01/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010672 Licensee Name: VITO LIOTINE
Firm: 001703 Firm Name: PRO ELECTRIC CORP.
Firm Phone: 718-625-1995  Firm Address: 68 JAY STREET BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $110.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TIBI ZICKERMAN
Owner Business Name: BROADWAY 21ST STREET LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  UP TO 100AMPS
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  SETS UP TO #2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  8/16 PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  STORE           
002  2L  16             
002  2R  16             
Buildings Total 11  36  12  11              
Total Units : 78 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 6 + New Meters 1 - Removed Meters 0 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/02/2013 Notice: 1 - FIRST NOTICE 11/26/2014
Power Issued: 02/02/2013 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A312566
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/21/2014 11/26/2014 TSO V E (70) (4) Y
INSPECTION COMMENTS: VIOLATIONS. DID NOT CHECK A/C STORE OR CASH WRAP RECEPTACLES
 
(2) 05/01/2015 05/06/2015 TS1 C R E (30) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A312566
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ALL RECEPTACLES NOT GROUNDED T-OUT 250.146
RSLV 11/21/2014 11/21/2014 05/01/2015
 
002 (999) OTHER
STORE RECEPTACLES SET BACK WOOD 314.20
RSLV 11/21/2014 11/21/2014 05/01/2015
 
003 (999) OTHER
STORE NEUTRAL BONDED LOAD SIDE SERVICE PANEL 250.20
RSLV 11/21/2014 11/21/2014 05/01/2015
 
004 (999) OTHER
APTS RECEPTACLE NOT GFCI PROTECTED KITCHEN 210.8
RSLV 11/21/2014 11/21/2014 05/01/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order