BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A303866
Premises: 49-62 VAN DAM STREET QUEENS BIN: 4003547     Block: 288   Lot: 1
   
Application Completed and Certified

Filed: 49-62 VAN DAM ST Census Tract:   199
1ST FL, MEZZANINE Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
DOB Cross Street(s):   LIE WB ENTRANCE VAN DAM ST,    BORDEN AVENUE
Status:   C - JOB IS SIGNED OFF 12/04/2012
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/28/2012 Job Start Date:   07/11/2012
Last Change:   12/04/2012 Job End Date:   07/11/2013
Appointment Status:   
Last Inspection By:   BOTSCH, E       On     11/15/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010830 Licensee Name: JERRY G SARABELLA
Firm: 002108 Firm Name: J. UNITED ELECT CONT'G CO
Firm Phone: 718-370-3000  Firm Address: 651 WILLOW BROOK ROAD STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $251.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   CAR REPAIR
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: KWALITY BUILDERS INC
Authorized Representative:  CBS OUTDOOR INC
Relationship To Owner:   X


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    36  32    10  36  10  42     
MEZ                 
Buildings Total 38  41    12  38     42         
Total Units : 176 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/28/2012 Notice: 1 - FIRST NOTICE 10/12/2012
Power Issued: 07/28/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A303866
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/04/2012 10/12/2012 EBT A E (45) (4) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 11/15/2012 11/21/2012 EBT C R E (30) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A303866
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
GARAGE GFI MISSING (GARAGE AREA)
RSLV 10/04/2012 10/04/2012 11/15/2012
 
002 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
GARAGE 2 WIRE UNDER LUG IN 100AMP DISCONNECT
RSLV 10/04/2012 10/04/2012 11/15/2012
 
003 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
GARAGE FUSE MISSING NO PINS ALLOWED
RSLV 10/04/2012 10/04/2012 11/15/2012
 
004 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
GARAGE LEFT 2 WIRE UNDER LUG ON LIFTS
RSLV 10/04/2012 10/04/2012 11/15/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.