BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A301272
Premises: 34-42 9 STREET QUEENS BIN: 4003834     Block: 323   Lot: 45
   
Application Completed and Certified

Filed: 34-42 9 ST Census Tract:   39
ALL Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
Related Job Number:    420548893
DOB Cross Street(s):    34 AVENUE,    35 AVENUE
Status:   C - JOB IS SIGNED OFF 10/24/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/09/2012 9:39 AM
Application Entered:   04/09/2012 Job Start Date:   04/10/2012
Last Change:   10/24/2012 Job End Date:   12/28/2012
Appointment Status:   
Last Inspection By:   THEODORE JUNSCH       On     10/12/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 012074 Licensee Name: RAVI MANGROO
Firm: 003771 Firm Name: GUIDING LIGHT ELECTRIC IN
Firm Phone: 718-847-5700  Firm Address: 125-18 101ST AVENUE, 1FL S. RICHMOND.HILL,QUEENS NY 11419 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $248.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   E - Four Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MOHAMED MEDHAT
Owner Business Name: ASTORIA CAPITOL LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  5  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  10  13  10             
001  10  14  10             
002  10  14  10             
002  10  13  10             
Buildings Total 40  54  32  40                
Total Units : 174 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 5 #4-Wire 0 #10-Wire 0
Existing Meters 4 + New Meters 1 - Removed Meters 0 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/09/2012 Notice:  
Power Issued: 04/09/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REWIRE HOUSE ADD A PLP METER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A301272
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/12/2012 10/17/2012 TJ1 C E (60) (0) Y
INSPECTION COMMENTS: CERTIFICATE




If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order