BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A298916
Premises: 155-55 CROSS BAY BOULEVARD QUEENS BIN: 4442269     Block: 11588   Lot: 75
   
Application Completed and Certified

Filed: 155-55 CROSSBAY BLVD Census Tract:   884 Health Area:  3611
11033-H.B. APTS. Admin Area:   A - QUEENS Inspection Area:   L
QUEENS, NY 11414 Community Board:   410
Special Place Name:   HOWARD BEACH SENIOR HOUSING
DOB Cross Street(s):   BELT PY EB EN CROSS BAY BLVD NB,    156 AVENUE
Status:   C - JOB IS SIGNED OFF 09/09/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/08/2011 9:03 AM
Application Entered:   12/08/2011 Job Start Date:   12/27/2011
Last Change:   09/09/2013 Job End Date:   06/30/2013
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     08/27/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010191 Licensee Name: RONALD J SPIELER
Firm: 001367 Firm Name: SPIELER & RICCA ELEC'L CO
Firm Phone: 718-392-4100  Firm Address: 52-09 VAN DAM STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:        Submittal #:   
Owner / Occup:
Owner Business Name: MONADNOCK CONSTRUCTION
Authorized Representative:  ALEKSANDR YELIZAROV
Relationship To Owner:   MONADNOCK PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1-400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  2  1-1600A / 1-3000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  100  96-3#4BX / 2-4#6 / 2-4#1
B. Over #2 to 1/0  6  4-4#3 / 2-4#1/0
C. Over 1/0 to 250 MCM  2  2-4#3/0
D. Over 250 MCM  20  10-4#500/6-4#600/4-4#350
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  96  96-1P3W 120/208V
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  9  7-200A / 2-100A 120/208V
D. 3 Phase Over 225 AMPS  4  1-1600A / 3-400A 120/208V
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    90  35    30  90  26     
001    305  453  39  207  305             
002    168  434  45  166  168             
003    168  434  45  166  168             
004    168  434  45  166  168             
ROF    36    36  30  15     
ROF  BLKHD            80  15     
Buildings Total 935  1798  174  740  935     121     23      
Total Units : 4726 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 96 #4-Wire 2 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/08/2011 Notice: 1 - FIRST NOTICE 08/05/2013
Power Issued: 12/08/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  11033-HOWARD BEACH SENIOR HOUSING-JOB FILED UNDER 2005 NEC CODE WITH NYC 2005 AMENDMENTS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A298916
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/30/2013 08/05/2013 COB A G (130) (5) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 08/27/2013 09/04/2013 FWE C R E (75) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A298916
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT SERVICE ENTRANCE RACEWAY BONDING JUMPER ON SUPPLY SIDEOF SERVICE DAISY CHAINED TO BE SIZED AT 12 1/2 PERCENT 250.102
RSLV 07/30/2013 07/30/2013 08/27/2013
 
002 (999) OTHER
BASEMENT SERVICE ROOM TROUGH BELOW FIRE ALARM FUSE CUT-OUT LINEAND LOAD IN THE SAME RACEWAY 230.7
RSLV 07/30/2013 07/30/2013 08/27/2013
 
003 (999) OTHER
1ST FL ELECTRICAL ROOM NO LIGHTING OUTLET PROVIDED 210.70 (C)
RSLV 07/30/2013 07/30/2013 08/27/2013
 
004 (999) OTHER
ROOF PANEL MULTIWIRE CIRCUIT APPROVED HANDLE TIE NOT PROVIDED 210.4
RSLV 07/30/2013 07/30/2013 08/27/2013
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF A/C UNIT SEALTIGHT NO GROUND IN SEALTIGHT FOR CONDUCTORSFUSED AT 30A
RSLV 07/30/2013 07/30/2013 08/27/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back