Electrical Application Details for App #: A298352
Premises: 171-03 68 AVENUE QUEENS BIN: 4149641     Block: 6925   Lot: 30
   
Application Completed and Certified

Filed: 171-03 68 AV Census Tract:   1223 Health Area:  2021
CELLAR-3RD FLOOR Admin Area:   A - QUEENS Inspection Area:   E
QUEENS, NY 11365 Community Board:   408
Related Job Number:    420466944
DOB Cross Street(s):    171 STREET,    172 STREET
Status:   C - JOB IS SIGNED OFF 06/26/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/11/2011 2:45 PM
Application Entered:   11/11/2011 Job Start Date:   11/11/2011
Last Change:   06/26/2013 Job End Date:   12/30/2011
Appointment Status:   
Last Inspection By:   BOTSCH, E       On     06/20/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011196 Licensee Name: PRAMANAND RAMBHAROSE
Firm: 002163 Firm Name: WINDSOR ELEC CONT'G INC.
Firm Phone: 718-850-6523  Firm Address: 95-01 BRISBIN STREET JAMAICA NY 11435 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $159.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: P MIZRA
Owner Business Name: YORK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    10  12    10             
001    15  20    10  15         
002    15  20    10  15         
003    15  20    10  15         
Buildings Total 55  72    38  55     10           
Total Units : 230 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/11/2011 Notice: 1 - FIRST NOTICE 06/04/2013
Power Issued: 11/11/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONVERT TO 2 FAMILY, SERVICE UPGRADE & GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A298352
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/22/2013 02/26/2013 EBT J G (45) (0) Y
INSPECTION COMMENTS: JOB IN PROGRESS NO COMMENTS
 
(2) 03/19/2013 03/26/2013 DNM N (15) (0) Y
INSPECTION COMMENTS: NO ACCESS CONTRACTOR DID NOT SHOW UP
 
(3) 05/24/2013 06/04/2013 COB V E (70) (12) Y
INSPECTION COMMENTS: VIOLATIONS
 
(4) 06/20/2013 06/26/2013 EBT C R E (45) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A298352
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BASEMENT & 1ST FLOOR PANELS
RSLV 05/24/2013 05/24/2013 06/20/2013
 
002 (999) OTHER
BASEMENT PANEL TWO CONDUCTORS ON BREAKER TERMIALS LISTED FORONE 110.14(A)
RSLV 05/24/2013 05/24/2013 06/20/2013
 
003 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
BASEMENT GFCI NEXT TO STEAM ROOM SHEETROCK SCREW USED TO FASTENRECEPTACLES
RSLV 05/24/2013 05/24/2013 06/20/2013
 
004 ( 53) GFCI HAS NOT BEEN PROVIDED
1ST FLOOR KITCHEN PENINSULAR
RSLV 05/24/2013 05/24/2013 06/20/2013
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
2ND FLOOR BALCONY
RSLV 05/24/2013 05/24/2013 06/20/2013
 
006 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
1ST FLOOR KITCHEN COUNTERTOP GFCI NO POWER
RSLV 05/24/2013 05/24/2013 06/20/2013
 
007 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
2ND FLOOR BEDROOM RECEPTACLES (MIDDLE BEDROOM)
RSLV 05/24/2013 05/24/2013 06/20/2013
 
008 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
ATTIC FIXTURE
RSLV 05/24/2013 05/24/2013 06/20/2013
 
009 ( 19) DEFECTIVE WIRING IS IN USE
GARAGE BOILER ROOM FEED TO BE TERMINATED IN BOX
RSLV 05/24/2013 05/24/2013 06/20/2013
 
010 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
GARAGE BOILER ROOM SWITCH BOX
RSLV 05/24/2013 05/24/2013 06/20/2013
 
011 ( 29) OUTLET BOXES ARE NOT COVERED
GARAGE CEILING RECEPTACLE
RSLV 05/24/2013 05/24/2013 06/20/2013
 
012 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTSIDE A/C DISCONNECT
RSLV 05/24/2013 05/24/2013 06/20/2013