BIS Menu  |  Electrical Applications   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A295155
Premises: 14-31 28 AVENUE QUEENS BIN: 4006077     Block: 539   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 14-31 28 AV Census Tract:   83 Health Area:  0300
WHOLE BUILDING Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
Related Job Number:    420189888
DOB Cross Street(s):    14 STREET,    21 STREET
Status:   C - JOB IS SIGNED OFF 03/12/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/22/2011 1:20 PM
Application Entered:   06/22/2011 Job Start Date:   06/23/2011
Last Change:   03/12/2016 Job End Date:   06/01/2013
Appointment Status:   
Last Inspection By:   BASDEO, C       On     02/25/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011539 Licensee Name: ALEXANDER LEVIN
Firm: 003051 Firm Name: A.L. ELECTRICAL CORP.
Firm Phone: 212-206-9141  Firm Address: 307 7TH AVENUE-SUITE 404 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $731.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 8 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ENACHE ANTON
Owner Business Name: 14-31 28TH AVE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  9  (8) 3 #6 WIR. (1) 4#2 W
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4 # 3/0
D. Over 250 MCM  1  4 WIRES, 350MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  10/20 60AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    30  20    10  30         
SWL    10        10             
001    12  21  12         
002    14  30  10  14         
003    14  30  10  14         
004    20  35  14  20         
PEN    10         
Buildings Total 108  146  18  59  108     16           
Total Units : 455 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 8 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 10 - Removed Meters 0 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/22/2011 Notice: 1 - FIRST NOTICE 02/11/2016
Power Issued: 06/22/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A295155
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/11/2016 02/11/2016 COB V (60) (4)
INSPECTION COMMENTS: OBJECTIONS ISSUED
 
(2) 02/25/2016 02/25/2016 COB C R (40) (0)
INSPECTION COMMENTS: OBJECTION REMOVED

OBJECTION FOR APPLICATION #: A295155
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) ALL APARTMENTS BALCONY, GFCI RECEPTACLES NOT WR - 406.8
RSLV 02/11/2016 02/11/2016 02/25/2016
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT)SERVICE TROUGH, MISSING BONDING JUMPER ON MIGB BUSHING TO BONDENCLOSURE
RSLV 02/11/2016 02/11/2016 02/25/2016
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT)OFFICE SUB PANEL, GROUNDING BAR REQUIRED FOR EQUIPMENT GROUNDINGCONDUCTORS
RSLV 02/11/2016 02/11/2016 02/25/2016
 
004 (999) OTHER
(BASEMENT)TWO 200 A SERVICE SWITCHES, NEUTRAL BAR IS NOT BONDED - 250.28
RSLV 02/11/2016 02/11/2016 02/25/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.