| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
INSP ID |
FIELD DATE |
DISP DATE |
INSP ID |
FLD DISP |
OBJ DISP |
ENRG REC |
TIME INSP |
REINSP DATE |
NEW OBJ |
APPT FLAG |
| |
| (1) |
02/18/2010 |
02/19/2010 |
TJ1 |
W |
|
|
(10) |
|
(3) |
|
| INSPECTION COMMENTS:
|
VIOLATIONS
|
| |
| (2) |
07/21/2017 |
07/21/2017 |
DEX |
N |
|
|
(25) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
CONTRACTOR NO SHOW
|
| |
| (3) |
08/24/2017 |
08/24/2017 |
ECH |
N |
|
|
(20) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
CONTRACTOR NO SHOW, NO ANSWER FOR PHONE
|
| |
| (4) |
09/27/2017 |
09/27/2017 |
NRS |
N |
|
|
(20) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
CONTRACTOR NO SHOW, CALLED, NO ANSWERE.
|
| |
| (5) |
10/06/2017 |
10/06/2017 |
NRS |
V |
X |
|
(6) |
|
(12) |
|
| INSPECTION COMMENTS:
|
(2)12BY12 BOXES NOT INSPECTED, TEMP POWER CONNECTED TO THESE. LOAD CALCULATION NEEDED FOR OPPOSITE SIDE METER BANK FED FROM RIGHT HAND SIDE 400A DISCONNECT THROUGH #2AWG FEEDERS. WORK DESCRIPTION NOT FILLED IN PROPERLY.
|
| |
| (6) |
02/16/2018 |
02/16/2018 |
MBE |
N |
|
|
(30) |
|
(0) |
Y |
| INSPECTION COMMENTS:
|
NO SHOW - INSPECTOR CONTACTED FIRM, LEFT A MESSAGE, AND WAITING IN APT BUILDING COMPLEX FOR CONTRACTOR TO SHOW UP.
|
| |
| (7) |
03/21/2018 |
03/21/2018 |
AGF |
J |
Y |
|
(45) |
|
(0) |
|
| INSPECTION COMMENTS:
|
PRIOR OBJECTION STILL EXIST.. FAIL |||
|
| |
| (8) |
05/31/2018 |
05/31/2018 |
MYT |
C |
R |
|
(45) |
|
(0) |
|
| INSPECTION COMMENTS:
|
JOB CERTIFIED
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 3) |
APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE (ALL FLOORS) BASEMENT HOUSE PANEL FEEDER SPLICE BOX |
RSLV |
02/18/2010 |
02/18/2010 |
03/21/2018 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) BASEMENT SPLICE BOX,SPLIT BOLT CONNECTORS AREONLY RATED FOR TWO CONDUCTORS |
RSLV |
02/18/2010 |
02/18/2010 |
03/21/2018 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS) BASEMENT MAIN GROUNDING CONDUCTOR NOT TERMINATEDAT WATER MAIN |
RSLV |
02/18/2010 |
02/18/2010 |
05/31/2018 |
| |
| 004 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) UNDERSIZED & BONDING SCREW NOT INSTALLED |
RSLV |
10/06/2017 |
10/06/2017 |
05/31/2018 |
| |
| 005 |
(123) |
SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED (BASEMENT) & HOUSE PANEL NOT MARKED |
RSLV |
10/06/2017 |
10/06/2017 |
03/21/2018 |
| |
| 006 |
(125) |
PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE (BASEMENT) HOUSE PANEL |
RSLV |
10/06/2017 |
10/06/2017 |
03/21/2018 |
| |
| 007 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (BASEMENT) HOUSE PANEL |
RSLV |
10/06/2017 |
10/06/2017 |
03/21/2018 |
| |
| 008 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT)#6AWG TAPCONDUCTORS IN 5'BY10" SPLICEBOX FOR METER B1 ARE NOTPROTECTED 240.21 |
RSLV |
10/06/2017 |
10/06/2017 |
03/21/2018 |
| |
| 009 |
(247) |
SIMULTANEOUS OPENING OF POLES (BASEMENT) HOUSE PANEL |
RSLV |
10/06/2017 |
10/06/2017 |
03/21/2018 |
| |
| 010 |
(280) |
MAIN BONDING JUMPER IS DEFECTIVE (BASEMENT) UNDERSIZED |
RSLV |
10/06/2017 |
10/06/2017 |
05/31/2018 |
| |
| 011 |
( 41) |
LOCKNUTS ARE NOT MADE UP TIGHT (BASEMENT) RIGHT SIDE 400A SERV DISC |
RSLV |
10/06/2017 |
10/06/2017 |
05/31/2018 |
| |
| 012 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (BASEMENT) HOUSE PANEL |
RSLV |
10/06/2017 |
10/06/2017 |
03/21/2018 |
| |
| 013 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT) - |
RSLV |
10/06/2017 |
10/06/2017 |
05/31/2018 |
| |
| 014 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (BASEMENT) GROUND BAR USED UNDER RIGHT HANDSIDE 400A SERV. DISC. |
RSLV |
10/06/2017 |
10/06/2017 |
03/21/2018 |
| |
| 015 |
(999) |
OTHER (BASEMENT) GEC CONDUIT NOT CONTINUOUS 250.64 |
RSLV |
10/06/2017 |
10/06/2017 |
05/31/2018 |