Electrical Application Details for App #: A284077
Premises: 94-16 34 ROAD QUEENS BIN: 4035807     Block: 1455   Lot: 60
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 94-16 34 RD Census Tract:   273 Health Area:  1012
BASEMENT/CC#4434662 Admin Area:   A - QUEENS Inspection Area:   D
QUEENS, NY 11372 Community Board:   403
DOB Cross Street(s):    94 STREET,    JUNCTION BOULEVARD
Status:   C - JOB IS SIGNED OFF 05/31/2018
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   04/11/2017 Job Start Date:   04/11/2017
Last Change:   05/31/2018 Job End Date:   04/11/2018
Appointment Status:   
Last Inspection By:   RILEY (MONTY) MONTAGUE       On     05/31/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $190.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PRETTI MIRANI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 44 + New Meters 1 - Removed Meters 1 = Total Meters 44

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 04/11/2017 Notice: C - CALL TO OFFICE 10/06/2017
Power Issued: 04/11/2017 Response: F - FILED TO REMOVE OBJECTION 04/11/2017

Follow-Up: X - FILED APPL,NOW CLOSED 04/11/2017
Contractor's Comments:  WE ARE ALSO COMPLETING WORK FILED FOR UNDER APP #A295422. WE ARE COMPLETEING THE FEEDER FROM SSW ON RIGHT TO THE CON EDEL BOX AND THE GROUNDING SYSTEM.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A284077
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/18/2010 02/19/2010 TJ1 W (10) (3)
INSPECTION COMMENTS: VIOLATIONS
 
(2) 07/21/2017 07/21/2017 DEX N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(3) 08/24/2017 08/24/2017 ECH N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW, NO ANSWER FOR PHONE
 
(4) 09/27/2017 09/27/2017 NRS N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW, CALLED, NO ANSWERE.
 
(5) 10/06/2017 10/06/2017 NRS V X (6) (12)
INSPECTION COMMENTS: (2)12BY12 BOXES NOT INSPECTED, TEMP POWER CONNECTED TO THESE. LOAD CALCULATION NEEDED FOR OPPOSITE SIDE METER BANK FED FROM RIGHT HAND SIDE 400A DISCONNECT THROUGH #2AWG FEEDERS. WORK DESCRIPTION NOT FILLED IN PROPERLY.
 
(6) 02/16/2018 02/16/2018 MBE N (30) (0) Y
INSPECTION COMMENTS: NO SHOW - INSPECTOR CONTACTED FIRM, LEFT A MESSAGE, AND WAITING IN APT BUILDING COMPLEX FOR CONTRACTOR TO SHOW UP.
 
(7) 03/21/2018 03/21/2018 AGF J Y (45) (0)
INSPECTION COMMENTS: PRIOR OBJECTION STILL EXIST.. FAIL |||
 
(8) 05/31/2018 05/31/2018 MYT C R (45) (0)
INSPECTION COMMENTS: JOB CERTIFIED

OBJECTION FOR APPLICATION #: A284077
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
(ALL FLOORS) BASEMENT HOUSE PANEL FEEDER SPLICE BOX
RSLV 02/18/2010 02/18/2010 03/21/2018
 
002 (999) OTHER
(ALL FLOORS) BASEMENT SPLICE BOX,SPLIT BOLT CONNECTORS AREONLY RATED FOR TWO CONDUCTORS
RSLV 02/18/2010 02/18/2010 03/21/2018
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) BASEMENT MAIN GROUNDING CONDUCTOR NOT TERMINATEDAT WATER MAIN
RSLV 02/18/2010 02/18/2010 05/31/2018
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) UNDERSIZED & BONDING SCREW NOT INSTALLED
RSLV 10/06/2017 10/06/2017 05/31/2018
 
005 (123) SERVICE DISCONNECTS ARE NOT PROPERLY GROUPED/LABELED
(BASEMENT) & HOUSE PANEL NOT MARKED
RSLV 10/06/2017 10/06/2017 03/21/2018
 
006 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(BASEMENT) HOUSE PANEL
RSLV 10/06/2017 10/06/2017 03/21/2018
 
007 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(BASEMENT) HOUSE PANEL
RSLV 10/06/2017 10/06/2017 03/21/2018
 
008 ( 19) DEFECTIVE WIRING IS IN USE
(BASEMENT)#6AWG TAPCONDUCTORS IN 5'BY10" SPLICEBOX FOR METER B1 ARE NOTPROTECTED 240.21
RSLV 10/06/2017 10/06/2017 03/21/2018
 
009 (247) SIMULTANEOUS OPENING OF POLES
(BASEMENT) HOUSE PANEL
RSLV 10/06/2017 10/06/2017 03/21/2018
 
010 (280) MAIN BONDING JUMPER IS DEFECTIVE
(BASEMENT) UNDERSIZED
RSLV 10/06/2017 10/06/2017 05/31/2018
 
011 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
(BASEMENT) RIGHT SIDE 400A SERV DISC
RSLV 10/06/2017 10/06/2017 05/31/2018
 
012 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(BASEMENT) HOUSE PANEL
RSLV 10/06/2017 10/06/2017 03/21/2018
 
013 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) -
RSLV 10/06/2017 10/06/2017 05/31/2018
 
014 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(BASEMENT) GROUND BAR USED UNDER RIGHT HANDSIDE 400A SERV. DISC.
RSLV 10/06/2017 10/06/2017 03/21/2018
 
015 (999) OTHER
(BASEMENT) GEC CONDUIT NOT CONTINUOUS 250.64
RSLV 10/06/2017 10/06/2017 05/31/2018