Electrical Application Details for App #: A273623
Premises: 30-11 21 STREET QUEENS BIN: 4533605     Block: 549   Lot: 14
   
Application Completed and Certified

Filed: 30-11 21 ST Census Tract:   79 Health Area:  0300
RESIDENTIAL BUILDING Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
Related Job Number:    402535912
DOB Cross Street(s):    30 AVENUE,    30 ROAD
Status:   C - JOB IS SIGNED OFF 03/04/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/24/2008 12:48 PM
Application Entered:   11/24/2008 Job Start Date:   11/25/2008
Last Change:   03/04/2011 Job End Date:   11/25/2009
Appointment Status:   
Last Inspection By:   BOTSCH, E       On     03/01/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012172 Licensee Name: GEORGIOS RODAS
Firm: 003883 Firm Name: RODEL ELEC'L CONTR'S, IN
Firm Phone: 718-784-1460  Firm Address: 31-29 VERNON BOULEVARD LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
7 - HVAC WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $309.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   RESIDENTIAL BUILDING
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOHN LIVADAROS
Owner Business Name: TWENTY FIRST ASTORIA LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    30                   
GND    30                   
002    50  75  40               
003    50  75  40               
004    50  75  40               
005    50  75  40               
006    50  75  40               
007    50  75  40               
Buildings Total 360  450  30  246                  
Total Units : 1086 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/14/2010
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A273623
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/08/2010 01/14/2010 EBT A (45) (4)
INSPECTION COMMENTS: VIOLATIONS
 
(2) 03/01/2011 03/04/2011 EBT C R (105) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A273623
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 32) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN JUNCTION BOX
ALL FLOOR - WIRE COUNT ON BAR BOX & 1900 THROUGHOUT
RSLV 01/08/2010 01/08/2010 03/01/2011
 
002 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
A11 FLOOR - SECURE WIRE WITHIN 12" OF BOX
RSLV 01/08/2010 01/08/2010 03/01/2011
 
003 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
ALL FLOOR - BOX CABLE TOUCHING WATER PIPER
RSLV 01/08/2010 01/08/2010 03/01/2011
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ALL FLOOR - MC CABLE TO BE BOND TO BOXES
RSLV 01/08/2010 01/08/2010 03/01/2011