Electrical Application Details for App #: A273136
Premises: 31-66 31 STREET QUEENS BIN: 4540364     Block: 589   Lot: 67
   
Application Completed and Certified

Filed: 3172 31 ST Census Tract:   61 Health Area:  0400
BSMT, 1-7 Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11106 Community Board:   401
Related Job Number:    402579367
DOB Cross Street(s):    31 AVENUE,    BROADWAY
Status:   C - JOB IS SIGNED OFF 01/29/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/04/2008 11:54 AM
Application Entered:   11/04/2008 Job Start Date:   11/05/2008
Last Change:   01/29/2010 Job End Date:   11/05/2009
Appointment Status:   
Last Inspection By:   THEODORE JUNSCH       On     01/13/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 010659 Licensee Name: PETER J GIOELLO
Firm: 000117 Firm Name: AMBER LITE ELECTRIC CORP.
Firm Phone: 718-605-5200  Firm Address: 441 WILD AVE 2ND FLOOR STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $4,607.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   
Owner / Occup: BRANKO MUSTAC
Owner Business Name: METRON CONTRACTING
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  3  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  67  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  12  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  65  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    69    69  40         
001    33    33  33             
002    106  195  30  106  106             
003    77  174  31  77  77             
004    85  179  31  85  85             
005    83  171  29  83  83             
006    75  155  75  75             
007    33  70  12  33  33             
Buildings Total 561  958  139  501  561     40           
Total Units : 2760 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 65 #4-Wire 3 #10-Wire 1
Existing Meters 0 + New Meters 69 - Removed Meters 0 = Total Meters 69

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/04/2008 Notice:  
Power Issued: 11/04/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A273136
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/21/2009 12/28/2009 COB J G (105) (0) Y
INSPECTION COMMENTS: KO'S SEALS FOR PANEL IN SERVICE RM,PANIC BAR FOR SERVICE RM DOOR, GFCI FOR GARAGE RECEPTACLES,COMPACTOR ROOM NEUTRALS TO BE ISOLATED IN DISCONNECT SWITCH,RECEPTACLES THROUGHOUT TO BE BONDED
 
(2) 01/13/2010 01/19/2010 TJ1 C E (60) (0) Y
INSPECTION COMMENTS: CERTIFICATE