BIS Menu   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A272422
Premises: 191-11 WOODHULL AVENUE QUEENS BIN: 4231505     Block: 10820   Lot: 83
   

DOB NOW: Inspections


Filed: 191-11 WOODHULL AV Census Tract:   500 Health Area:  2820
BSMT,1ST FLOOR Admin Area:   A - QUEENS Inspection Area:   J
QUEENS, NY 11423 Community Board:   412
DOB Cross Street(s):    191 STREET,    193 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   10/06/2008 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   ENDRULAT, P.       On     09/29/2008      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: JAMES EISENBERG
Owner Business Name: GRAND REVIEW LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 10/06/2008
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 10/06/2008
Contractor's Comments:  CC# 4374002

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A272422
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/29/2008 10/06/2008 PEN W (15) (8)
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: A272422
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
1ST FL RT SIDE FIXTURES, REC, SWITCHES, & PANEL
OPEN 09/29/2008 09/29/2008
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT BY WATER METER RACEWAY NOT COMPLETED
OPEN 09/29/2008 09/29/2008
 
003 ( 19) DEFECTIVE WIRING IS IN USE
A-1ST FL APT RT SIDE APT OPEN WIRING, WIRE BURIED IN CEILING
OPEN 09/29/2008 09/29/2008
 
004 ( 19) DEFECTIVE WIRING IS IN USE
B-BSMT SVC AREA OPEN WIRING & OPEN SPLICE
OPEN 09/29/2008 09/29/2008
 
005 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
1ST FL APT SPLICED #12 TO 8AWG TO PANEL
OPEN 09/29/2008 09/29/2008
 
006 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT 20A & 30A PROTECTING #14 WIRE
OPEN 09/29/2008 09/29/2008
 
007 ( 20) PLUG FUSES ARE NOT OF THE TAMPERPROOF TYPE
BSMT SVC AREA 20A & 30A
OPEN 09/29/2008 09/29/2008
 
008 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
BSMT FOR ENTIRE BLDG LOAD
OPEN 09/29/2008 09/29/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.