Electrical Application Details for App #: A269353
Premises: 11-02 49 AVENUE QUEENS BIN: 4864704     Block: 62   Lot: 46
   
Application Completed and Certified

Filed: 11-02 49 AV Census Tract:   7 Health Area:  0720
ENTIRE Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    402474675
DOB Cross Street(s):    11 STREET,    11 PLACE
Status:   C - JOB IS SIGNED OFF 11/09/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/18/2008 1:38 PM
Application Entered:   06/18/2008 Job Start Date:   06/18/2008
Last Change:   11/09/2009 Job End Date:   06/01/2009
Appointment Status:   
Last Inspection By:   BASDEO, C       On     10/23/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011225 Licensee Name: ZVI GELB
Firm: 002626 Firm Name: ZEREM ELECTRIC CORP.
Firm Phone: 718-377-8685  Firm Address: 3011 AVENUE L BROOKLYN NY 11210 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   47966     Submittal #: 07A0286  
Owner / Occup: PAUL ALBA
Owner Business Name: THE J COMPANIES
Authorized Representative:  PAUL ALBA
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  2  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  126  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  19  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  123  
C. 3 Phase Up to 225 AMPS  7  
D. 3 Phase Over 225 AMPS  4  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 1925  2290  355  1340  1925     50           
Total Units : 7885 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 123 #4-Wire 3 #10-Wire 1
Existing Meters 0 + New Meters 127 - Removed Meters 0 = Total Meters 127

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/18/2008 Notice: 1 - FIRST NOTICE 08/10/2009
Power Issued: 06/18/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A269353
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/05/2009 08/10/2009 COB V G (165) (8) Y
INSPECTION COMMENTS: VIOLATIONS
 
(2) 09/02/2009 09/08/2009 COB J Y (75) (0) Y
INSPECTION COMMENTS: REVISE PRINT CANNOT BE LOCATED
 
(3) 10/23/2009 10/27/2009 COB C R E (15) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A269353
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
BASEMENT AND GARAGE OUTLET
RSLV 08/05/2009 08/05/2009 09/02/2009
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF NO GROUNDING CONDUCTOR IN SEALTIGHT TO A/C UNITS
RSLV 08/05/2009 08/05/2009 09/02/2009
 
003 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BASEMENT SERVICE INSTALLATION NOT TO APPROVE DRAWING FEED TO FIREPUMP#2 NOT 1/0,HP-C SERVICE ROOM RETAIL TROUGH RELOCATE FIRE PUPM SW
RSLV 08/05/2009 09/02/2009 10/23/2009
 
004 (999) OTHER
BASEMENT SERVICE ROOM DOORS TO HAVE PANIC BARS 110.26C2
RSLV 08/05/2009 08/05/2009 09/02/2009
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT SERVICE ROOM PIPES FOR FEEF FROM HP-4,HP-8 TO BE BONDEDTO FRAME OF SWITCH
RSLV 08/05/2009 08/05/2009 09/02/2009
 
006 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BASEMENT STORAGE ROOM BOX NOT SUPPORTED
RSLV 08/05/2009 08/05/2009 09/02/2009
 
007 (999) OTHER
APARTMENTS ALL GFCI RECEPTACLES BONDING JUMPER FOR RECEPTACLESIS NOT PROVIDED
RSLV 08/05/2009 08/05/2009 09/02/2009
 
008 (999) OTHER
BASEMENT A/C DISCONNECT NO READILY ACCESSIBLE 440.14
RSLV 08/05/2009 08/05/2009 09/02/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.