| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
1 |
|
| E. Over 1200 AMPS |
2 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
126 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
19 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
123 |
|
| C. 3 Phase Up to 225 AMPS |
7 |
|
| D. 3 Phase Over 225 AMPS |
4 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 53) |
GFCI HAS NOT BEEN PROVIDED BASEMENT AND GARAGE OUTLET |
RSLV |
08/05/2009 |
08/05/2009 |
09/02/2009 |
| |
| 002 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ROOF NO GROUNDING CONDUCTOR IN SEALTIGHT TO A/C UNITS |
RSLV |
08/05/2009 |
08/05/2009 |
09/02/2009 |
| |
| 003 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BASEMENT SERVICE INSTALLATION NOT TO APPROVE DRAWING FEED TO FIREPUMP#2 NOT 1/0,HP-C SERVICE ROOM RETAIL TROUGH RELOCATE FIRE PUPM SW |
RSLV |
08/05/2009 |
09/02/2009 |
10/23/2009 |
| |
| 004 |
(999) |
OTHER BASEMENT SERVICE ROOM DOORS TO HAVE PANIC BARS 110.26C2 |
RSLV |
08/05/2009 |
08/05/2009 |
09/02/2009 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BASEMENT SERVICE ROOM PIPES FOR FEEF FROM HP-4,HP-8 TO BE BONDEDTO FRAME OF SWITCH |
RSLV |
08/05/2009 |
08/05/2009 |
09/02/2009 |
| |
| 006 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BASEMENT STORAGE ROOM BOX NOT SUPPORTED |
RSLV |
08/05/2009 |
08/05/2009 |
09/02/2009 |
| |
| 007 |
(999) |
OTHER APARTMENTS ALL GFCI RECEPTACLES BONDING JUMPER FOR RECEPTACLESIS NOT PROVIDED |
RSLV |
08/05/2009 |
08/05/2009 |
09/02/2009 |
| |
| 008 |
(999) |
OTHER BASEMENT A/C DISCONNECT NO READILY ACCESSIBLE 440.14 |
RSLV |
08/05/2009 |
08/05/2009 |
09/02/2009 |