BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A265981
Premises: 26-25 30 STREET QUEENS BIN: 4007815     Block: 598   Lot: 24
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 26-25 30 ST Census Tract:   71 Health Area:  0300
BASEMENT Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
DOB Cross Street(s):   ASTORIA BOULEVARD,    NEWTOWN AVENUE
Status:   C - JOB IS SIGNED OFF 08/08/2023
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/21/2008 12:00 PM
Application Entered:   02/21/2008 Job Start Date:   02/25/2008
Last Change:   08/08/2023 Job End Date:   02/25/2008
Appointment Status:   
Last Inspection By:   EVON GRANDISON       On     08/08/2023      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010431 Licensee Name: MICHAEL T MICHAEL
Firm: 000988 Firm Name: MICHAEL BROS. ELECT. CORP
Firm Phone: 718-204-7913  Firm Address: 20-65 STEINWAY STREET ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $55.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EVANGELOS THEOLOGIS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3 # 1 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 4 + New Meters 4 - Removed Meters 4 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/21/2008 Notice: 1 - FIRST NOTICE 02/25/2020
Power Issued: 02/21/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW ELECTRICAL OVERHEAD SERVICE. INSTALL OUTDOOR METERS. EXISTING RISERS AND PANELS TO REMAIN.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A265981
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/25/2020 02/25/2020 EVG V (62) (3)
INSPECTION COMMENTS: JOB FAILED.
 
(2) 07/22/2020 07/23/2020 ECH J Y (50) (0)
INSPECTION COMMENTS: FAIL, ALL OBJECTIONS HAVE NOT BEEN REMOVED, TO BE RE-INSPECTED WITH NEW PERMIT.
 
(3) 08/08/2023 08/08/2023 EVG C R (5) (0)
INSPECTION COMMENTS: JOB PASSED. REFER TO APPLICATION Q00375986 FOR THE SIGN OFF OF THE 4 SERVICE SWITCHES.

OBJECTION FOR APPLICATION #: A265981
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)CONTRACTOR NEEDS TO OPEN A NEW - Q - APPLICATION AND ADD ALL 4SERVICE SWITCHES.
RSLV 02/25/2020 02/25/2020 08/08/2023
 
002 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT)310.15 B, BREAKER NEED TO BE DE-RATED BASED ON THE NUMBER OFCONDUCTORS IN THE CONDUIT.
RSLV 02/25/2020 02/25/2020 07/22/2020
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(BASEMENT) 210.4, MULTI WIRE BRANCH CIRCUITS NEED 2 POLE BREAKERS.
RSLV 02/25/2020 02/25/2020 07/22/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back