BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A264704
Premises: 64-64 WETHEROLE STREET QUEENS BIN: 4072592     Block: 3098   Lot: 16
   
Application Completed and Certified

Filed: 64-61 AUSTIN ST Census Tract:   697.01 Health Area:  1930
BASE 1,2,3,4,5,6 Admin Area:   A - QUEENS Inspection Area:   D
QUEENS, NY 11374 Community Board:   406
Related Job Number:    402407668
DOB Cross Street(s):    64 ROAD,    65 ROAD
Status:   C - JOB IS SIGNED OFF 08/28/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/07/2008 9:30 AM
Application Entered:   01/07/2008 Job Start Date:   01/07/2008
Last Change:   08/28/2014 Job End Date:   03/07/2008
Appointment Status:   
Last Inspection By:   ASHMAN, K.       On     05/29/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011252 Licensee Name: ALBERT V DATTOLO
Firm: 001211 Firm Name: RAINBOW ELECTRIC CO., INC
Firm Phone: 718-521-0926  Firm Address: 76-18 ROCKAWAY BLVD WOODHAVEN NY 11421 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $767.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHARLES MALUL
Owner Business Name: GREEN STAR EQUITIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMP SW
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  9  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  SET 500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  8  20 POLE PANELS
C. 3 Phase Up to 225 AMPS  1  200AMP 3 PHASE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 52  127  18  32  32                
Total Units : 261 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 9 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 9 - Removed Meters 0 = Total Meters 9

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/07/2008 Notice: 1 - FIRST NOTICE 05/14/2014
Power Issued: 01/07/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW CONSTRUCTION OF EIGHT FAMILY TO HAVE 9 METERS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A264704
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/28/2014 01/31/2014 EBT Z (0) (0) Y
INSPECTION COMMENTS: NOT INSPECTED
 
(2) 02/20/2014 02/25/2014 EBT J G (30) (0) Y
INSPECTION COMMENTS: WATER GROUND TO BE INSPECTED. REST OF BUILDING OK
 
(3) 05/09/2014 05/14/2014 COB A G (25) (2) Y
INSPECTION COMMENTS: VIOLATIONS
 
(4) 05/29/2014 06/04/2014 KAS C R E (30) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A264704
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BASEMENT WATER MAIN GROUNDING CONDUCTOR UNDERSIZED, TO BE 1/0 FOR 500MCM SERVICE ENTRANCE
RSLV 05/09/2014 05/09/2014 05/29/2014
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BASEMENT SERVICE ROOM 200A SERVICE PANEL
RSLV 05/09/2014 05/09/2014 05/29/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order