BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A260952
Premises: 10-22 46 ROAD QUEENS BIN: 4000371     Block: 47   Lot: 43
   
Application Completed and Certified

Filed: 10-22 46 RD Census Tract:   7 Health Area:  0720
IFL,2FL,CELLAR AND OUT-DOOR. Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
DOB Cross Street(s):   VERNON BOULEVARD,    11 STREET
Status:   C - JOB IS SIGNED OFF 02/20/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/04/2007 7:06 PM
Application Entered:   09/04/2007 Job Start Date:   09/05/2007
Last Change:   02/20/2009 Job End Date:   11/20/2007
Appointment Status:   
Last Inspection By:   BOTSCH, E       On     02/17/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011011 Licensee Name: PETER BISHUN
Firm: 002349 Firm Name: PAC ELECTRIC CORP.
Firm Phone: 718-738-3813  Firm Address: 124-20 LIBERTY AVENUE RICHMOND HILL NY 11419 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $115.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VINCENT PITARO.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  2P100
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  12/24 CB.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 25  50  20                  
Total Units : 99 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/04/2007 Notice: 1 - FIRST NOTICE 10/07/2008
Power Issued: 09/04/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  I FLOOR,2 FLOOR,CELLAR AND OUT-DOOR.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A260952
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/01/2008 10/07/2008 EFF A G (45) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 02/17/2009 02/20/2009 EBT C R E (45) (0) Y
INSPECTION COMMENTS: COMPLETED

OBJECTION FOR APPLICATION #: A260952
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT SERVICE SW MAIN BREAKER IS NOT BOLTED IN 408.36F
RSLV 10/01/2008 10/01/2008 02/17/2009
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT FIXED EQUIP IN NOT PROPERLY GROUNDED (NEUTRAL NOT BONDED TOENCLOSURE) 250.112
RSLV 10/01/2008 10/01/2008 02/17/2009
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT KO ARE NOT CLOSED IN PANEL BOX (BSMT 200A COMBO) 110.12(A)
RSLV 10/01/2008 10/01/2008 02/17/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back