BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A257537
Premises: 21-26 GAR 30 AVENUE QUEENS BIN: 4531228     Block: 549   Lot: 26
   
Application Completed and Certified

Filed: 21-24 30 AV Census Tract:   79 Health Area:  0300
BUILDING Admin Area:   A - QUEENS Inspection Area:   A
QUEENS, NY 11102 Community Board:   401
Related Job Number:    402225908
DOB Cross Street(s):    21 STREET,    23 STREET
Status:   C - JOB IS SIGNED OFF 02/08/2008
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/19/2007 11:32 AM
Application Entered:   05/19/2007 Job Start Date:   05/19/2007
Last Change:   02/08/2008 Job End Date:   05/18/2010
Appointment Status:   
Last Inspection By:   THEODORE JUNSCH       On     02/04/2008      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011762 Licensee Name: RABINDRA N RAMGARIB
Firm: 003374 Firm Name: INDY ELECTRIC CORP.
Firm Phone: 718-323-4639  Firm Address: 120-21 101 AVENUE RICHMOND HILL NY 11419 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $2,807.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (2  Stores, 28 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KHAN SHIBBER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  28  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  2  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  28  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  8  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  28  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   600  30  335  340     40           
Total Units : 1345 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 28 #4-Wire 3 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/19/2007 Notice: 1 - FIRST NOTICE 01/23/2008
Power Issued: 05/19/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A257537
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/16/2008 01/23/2008 DAH V G (115) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 02/04/2008 02/08/2008 TJ1 C R E (60) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A257537
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
800A SERVICE SWITCH
RSLV 01/16/2008 01/16/2008 02/04/2008
 
002 (999) OTHER
BSMT RACEWAY UNDERSIZED BOND
RSLV 01/16/2008 01/16/2008 02/04/2008
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
BSMT TRANS S CAB. & 400A FP SERV & TROUGH
RSLV 01/16/2008 01/16/2008 02/04/2008
 
004 (999) OTHER
BSMT FP 400A SER SW NOT PAINTED RED
RSLV 01/16/2008 01/16/2008 02/04/2008



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order