Electrical Application Details for App #: A257420
Premises: 26-26 JACKSON AVENUE QUEENS BIN: 4003502     Block: 267   Lot: 19
   
Application Completed and Certified

Filed: 26-26 JACKSON AV Census Tract:   19 Health Area:  0720
ENTIRE BUILDING Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   402
Related Job Number:    402409149
DOB Cross Street(s):   PURVES STREET,    43 AVENUE
Status:   C - JOB IS SIGNED OFF 08/10/2009 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/15/2007 Job Start Date:   05/30/2007
Last Change:   08/10/2009 Job End Date:   09/30/2009
Appointment Status:   
Last Inspection By:   ENDRULAT, P.       On     07/29/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011749 Licensee Name: JEROME DALY
Firm: 003344 Firm Name: AMRA ELECTRICAL CORP
Firm Phone: 718-444-5209  Firm Address: 1415 UTICA AVENUE BROOKLYN NY 11201 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $4,997.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARCUS JEFFREY
Owner Business Name: 26-26 JACKSON AVE LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  2  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  41  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  
D. Over 250 MCM  13  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  40  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  2  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total 1300  1300  120  1000  1300     250          300 
Total Units : 5570 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 41 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 41 - Removed Meters 0 = Total Meters 41

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/15/2007 Notice: 1 - FIRST NOTICE 06/15/2009
Power Issued: 05/15/2007 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ENTIRE BUILDING,40 APARTMENT AND PUBLIC AREA

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A257420
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/15/2009 05/20/2009 PEN J G (225) (0) Y
INSPECTION COMMENTS: NOT READY
 
(2) 06/12/2009 06/15/2009 FWE A G (85) (5) Y
INSPECTION COMMENTS: NONE
 
(3) 07/15/2009 07/21/2009 PEN J Y G (30) (0) Y
INSPECTION COMMENTS: ALSO SEE APP# A266757 A/B PLAN NEED TO BE CHANGE
 
(4) 07/29/2009 08/03/2009 PEN C R E (30) (0) Y
INSPECTION COMMENTS: COMPLETED

OBJECTION FOR APPLICATION #: A257420
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A-BSMT MECHANICAL VENT TRANSFORMER 450.9
RSLV 06/12/2009 06/12/2009 07/15/2009
 
002 (999) OTHER
B-ALL CLOSETS NOT SUITABLE FOR CLOTHES CLOSETS 410.8B
RSLV 06/12/2009 06/12/2009 07/15/2009
 
003 (999) OTHER
C-BSMT NOT AS PER A/B DRAWINGS CAL# 49289
RSLV 06/12/2009 07/15/2009 07/29/2009
 
004 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
VARUIOUS ALL APTS BY GLASS DOOR & WINDOW
RSLV 06/12/2009 06/12/2009 07/15/2009
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
VARIOUS BALCONYS ALL APTS
RSLV 06/12/2009 06/12/2009 07/15/2009