BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: A148505
Premises: 40-27 29 STREET QUEENS BIN: 4004871     Block: 403   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 29-69 NORTHERN BLVD Census Tract:   27 Health Area:  0720
STREET Admin Area:   A - QUEENS Inspection Area:   C
QUEENS, NY 11101 Community Board:   401
DOB Cross Street(s):       
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/25/1998 Job Start Date:   06/15/1998
Last Change:   08/22/2025 Job End Date:   06/30/1998
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   KENNETH AMOS       On     09/08/1998      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  

License #: 009143 Licensee Name: SHELDON L BEIL
Firm: 003151 Firm Name: SHELDON ELECTRIC, INC.
Firm Phone: 718-937-3200  Firm Address: 42-14 CRESCENT STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
5 - FIRE DAMAGE
Total Fee:  $585.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   TRANSITE ACTHOUTS
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: LAQUILA CONLTUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  4  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
SUB FEEDERS (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                      150 
Total Units : 152 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

Access:   8:00 - 3:30 PM Contact Phone:   718-937-3200/102

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 06/25/1998 Notice: 1 - FIRST NOTICE 09/15/1998
Power Issued: 06/25/1998 Response:  

Follow-Up:
Wires Comments: NEED EMGENCY TEMP REPLACE ALL EQUIPMENT -PLEASE CALL CON ED
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A148505
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/24/1998 08/07/1998 JW1 Z (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 09/08/1998 09/15/1998 KAM A G (25) (4)
INSPECTION COMMENTS: 1/NEUT NOT BONDED 2/RACEWY NOT CONTINOUS TO GND CLAMP 27-3110C 3/GRD GOES TO NEUT OF 200 AMP SW NOT TO 400 AMP 3PHASE SW WHICH HAS NO NEU