Electrical Application Details for App #: A038681
Premises: 148-09 NORTHERN BOULEVARD QUEENS BIN: 4113236     Block: 5005   Lot: 7502
   
Application Completed and Certified

Filed: 148-09 NORTHERN BLVD Census Tract:   1163 Health Area:  1310
BOILER ROOM Admin Area:   A - QUEENS Inspection Area:   B
QUEENS, NY 11354 Community Board:   407
DOB Cross Street(s):    147 STREET,    149 STREET
Status:   C - JOB IS SIGNED OFF 06/17/2013
Request Type:   C - COMPLAINT eFiled:   YES
Application Entered:   02/14/2013 Job Start Date:   02/14/2013
Last Change:   06/17/2013 Job End Date:   02/28/2013
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     03/07/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011056 Licensee Name: BARRY SAXE
Firm: 002286 Firm Name: CEDAR ELEC'L CONT'RS INC.
Firm Phone: 212-594-2802  Firm Address: 369 WEST 34TH STREET 2ND FLR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $40.00
Other Work:   IMPROPER ELECTRIC
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: A.A. HILL CO., INC.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                     
Buildings Total                       
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice:  01/16/2013
Power Issued: Response: F - FILED TO REMOVE OBJECTION 02/14/2013

Follow-Up: X - FILED APPL,NOW CLOSED 02/14/2013
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: A038681
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/28/1989 04/19/1989 ROG N (25) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(2) 01/10/2013 01/16/2013 TJ1 W (45) (4) Y
INSPECTION COMMENTS: VIOLATIONS
 
(3) 03/07/2013 03/13/2013 DNM C R (15) (0) Y
INSPECTION COMMENTS: CERTIFICATE

OBJECTION FOR APPLICATION #: A038681
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
BOILER ROOM SUMP PUMP,FLEXIBLE CORD PERMANENT WIRING
RSLV 01/10/2013 01/10/2013 03/07/2013
 
002 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
BOILER ROOM CONDUIT NOT PROPERLY SUPPORTED THROUGHOUT
RSLV 01/10/2013 01/10/2013 03/07/2013
 
003 ( 19) DEFECTIVE WIRING IS IN USE
BOILER ROOM DISCONNECT SWITCHES THROUGHT OPEN SPLICES ANDNO COVERS
RSLV 01/10/2013 01/10/2013 03/07/2013
 
004 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
BOILER ROOM ARMOR CABLE NOT TERMINATED AT CIRCULATOR PUMP(FREE AIR SPLICE)
RSLV 01/10/2013 01/10/2013 03/07/2013