BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M388140
NO AHV RECORDS WERE FOUND FOR THIS BIN
Premises: 347 EAST 105 STREET MANHATTAN BIN: 1052758     Block: 1677   Lot: 22
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 347 E 105TH ST Census Tract:   170 Health Area:  2600
ALL BUILDING Admin Area:   M - MANHATTAN Inspection Area:   H
NEW YORK, NY 10029 Community Board:   111
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 09/26/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/24/2016 8:35 PM
Application Entered:   10/24/2016 Job Start Date:   10/26/2016
Last Change:   09/26/2017 Job End Date:   04/02/2017
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     09/25/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012152 Licensee Name: EDIN BECIROVIC
Firm: 003854 Firm Name: NEW KC ELECTRIC INC
Firm Phone: 718-392-0077  Firm Address: 36-32 23 STREET LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $967.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: STEVE HASKELL
Owner Business Name: 347 E 105TH STREET,LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30A
B. 101 Up to 200 AMPS  1  200A
C. 201 Up to 600 AMPS  1  400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  SET OF #10
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  SET OF 3/0
D. Over 250 MCM  1  SET OF 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  10  APARTMENT 24 CIRCUIT
C. 3 Phase Up to 225 AMPS  1  42 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL  BN  11  24  11             
CEL  PUB  17    22             
OSP  BACK  12         
LOB  ENTRY               
SWL  STAIR  14    14             
001  1N  13  25  13             
001  1S  14  31  10  14             
002  2E  21             
002  2W  16  37  10  16             
003  3E  15  37  15             
003  3W  15  37  15             
004  4E  15  37  15             
004  4W  15  37  15             
005  5N  14  30  14             
ROF  ROOF    10  24         
ROF  5TH F    10             
Buildings Total 191  338  42  105  196     36           
Total Units : 908 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/24/2016 Notice: 1 - FIRST NOTICE 09/08/2017
Power Issued: 10/24/2016 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW ELECTRICAL SERVICE AND RENOVATION OF ALL UNITS

 
Inspection Details
 

*NO AHV RECORDS WERE FOUND FOR THIS BIN
INSPECTION FOR APPLICATION #: M388140
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/08/2017 09/08/2017 GYM V (130) (3)
INSPECTION COMMENTS: OBJECTION
 
(2) 09/25/2017 09/26/2017 EDB C R (85) (0)
INSPECTION COMMENTS: INSPECT OBJECTION ONLY.

OBJECTION FOR APPLICATION #: M388140
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)KITCHENS AND BATH ROOMS MISSING TAMPER RESISTANT TYPE 406.11
RSLV 09/08/2017 09/08/2017 09/25/2017
 
002 (999) OTHER
(BASEMENT)400 AMP SERVICE BONDING JUMPER AND GROUNDING ELECTRODE CONDUCTORUNDER SIZE 250.66
RSLV 09/08/2017 09/08/2017 09/25/2017
 
003 (999) OTHER
(BASEMENT) OUTLET BOXES EXTENDER MISSING 314.20
RSLV 09/08/2017 09/08/2017 09/25/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order